OPERATOR MANUAL // SECTION 2: INSTALLATION
HONEYWELL
13
4. WIRE THE DETECTOR RELAYS.
a.
Insert the relay cables into the metal enclosure base through
one of the conduit openings.
b.
Connect the Fire Alarm wires to the 4 pin WECO terminal J3.
Install the wires into J4 Pins 3 and 4 (for
N
ormally
O
pen relays)
and firmly tighten down the slotted screws with a small
screwdriver.
c.
Connect the Fault wires to the four pin WECO terminal J5.
Install the wires into J5 Pins 1 and 2 (for Normally Closed
relays) and firmly tighten down the slotted screws with a small
screwdriver.
d.
If the Fire Verify option is used, connect the Verify Fire Alarm
wires to the four pin WECO terminal J6. Install the wires into J6
Pins 1 and 2 (for Normally Open relays) and firmly tighten down
the slotted screws with a small screwdriver.
Refer to Figure 4, Model SS4-AI Detector Wiring, for more
details on relay connections.
5. REPLACE THE DETECTOR MODULE INTO THE ENCLOSURE.
a.
Gently install the module back over the three metal standoffs
and screw it down with the three chrome-plated screws into the
standoffs. This secures the module to the enclosure.
b.
If necessary, clean the detectors and windowed cover according
to the instructions in Section 3.2.
c.
Screw down the metal enclosure top windowed cover until
secure and tighten the Allen-head "tamper-proof" screw.