9.1.3. Safety valve

1. Actuate lifting device
2. Release lifting device
• Shut-off valve closes
• available water flows completely off

Malfunction:

1. Actuate lifting device multiple times, if necessary initiate 

repairs

9.2. Maintenance

9.2.1. Pressure reducing valve

1. Close shutoff valve on inlet
2. Release pressure on outlet side (e.g. through water tap)
3. Close shutoff valve on outlet
4. Loosen slotted screw

• Do not remove slotted screw

5. Slacken tension in compression spring

• Turn adjustment handle counter clockwise (-) until it 

does not move any more

6. Unscrew spring bonnet

• Use double ring wrench ZR06K

7. Remove slip ring
8. Remove valve insert with a pair of pliers
9. Unscrew filter bowl

• Use double ring wrench ZR06K

10. Remove slotted ring
11. Check that sealing ring, edge of nozzle and slotted ring 

are in good condition, and if necessary replace the entire 
valve insert

12. Remove filter, clean and reinsert
13. Place O-ring onto filter bowl
14. Reassemble in reverse order

15. Set outlet pressure and adjust setting scale

9.2.2. Check valve

1. Close shutoff valve on inlet
2. Release pressure on outlet side (e.g. through water tap)
3. Close shutoff valve on outlet
4. Replace check valve
5. Slowly open shut off valves on inlet and outlet

9.3. Adjusting the setting scale

If the adjustment knob is removed, this setting is lost. A new 
setting can be achieved using a pressure gauge.
1. Close shutoff valve on inlet
2. Release pressure on outlet side (e.g. through water tap)
3. Close shutoff valve on outlet
4. Fit pressure gauge
5. Loosen slotted screw

• Do not remove slotted screw

6. Slowly open shutoff valve on inlet
7. Set desired outlet pressure (e.g. 4 bar)
8. Align scale (e.g. 4) in middle of viewing window
9. Retighten slotted screw
10. Slowly open shutoff valve on outlet

9.4. Cleaning

If necessary, the filter bowl and the filter can be cleaned.

1. Close shutoff valve on inlet
2. Release pressure on outlet side (e.g. through water tap)
3. Close shutoff valve on outlet
4. Unscrew filter bowl

• Use double ring wrench ZR06K

5. Remove filter, clean and reinsert
6. Place O-ring onto filter bowl
7. Screw in filter cup hand-tight (up to max. 18Nm)
8. Slowly open shutoff valve on inlet
9. Slowly open shutoff valve on outlet

10. Disposal

• Dezincification resistant brass housing 
• Brass threaded connections
• Stainless steel filter mesh on pressure reducing valve
• Transparent synthetic material filter bowl on pressure 

reducing valve

• High grade synthetic material pressure reducing valve 

insert, spring bonnet with adjuster knob, shutoff valves, 
test socket, check valve, safety valve insert and drain 
connector

• Fibre-reinforced NBR diaphragm
• NBR  seals
• EPP insulation shells

Frequency: every 6 month

Frequency: every 1-3 years (depending on local 
operating conditions)
To be carried out by an installation company

Caution !

There is a spring in the spring bonnet. It may cause 
injuries if the spring is derailing. 
• Make sure tension in compression spring is slak-

kened!

Press in diaphragm with finger before inserting slip ring
Screw in filter cup hand-tight (up to max. 18Nm)

To be carried out by an installation company

Caution !

Do not use any cleansers that contain solvents and/or 
alcohol for cleaning the plastic parts, because this can 
cause damage to the plastic components - water 
damage could result.

To be carried out by an installation company or  the 
operator.

Detergents must not be allowed to enter the environ-
ment or the sewerage system!

Observe the local requirements regarding correct 
waste recycling/disposal!

Summary of Contents for SG150 AA Series

Page 1: ...i di montaggio Anleitung zum späteren Gebrauch aufbewahren Keep instructions for later use Conserver la notice pour usage ultérieur Conservare le istruzioni per uso successivo Sicherheitsgruppe Safety Group Vanne de sécurité combinée Gruppo di sicurezza SG150 SG150D EBA SG150 D Rev A ...

Page 2: ...r Öffnungskraft wirkt eine mechanische Kraft Feder entgegen Das Absperrventil dient dazu den Rückflussverhinderer zu prüfen 3 Verwendung Für geschlossene Wassererwärmer bis 200 l nach DIN 4753 Teil 1 und DIN 1988 Bauteilgeprüft gemäß TRD 721 für den Druckbereich 1 10 bar 4 Technische Daten 5 Lieferumfang Die Sicherheitsgruppe besteht aus Gehäuse mit Prüfstutzen G 1 4 Verschraubungen Varianten AA A...

Page 3: ...tageanleitung 1 Rohrleitung gut ausblasen oder ausspülen 2 Sicherheitsgruppe in die Kaltwasserleitung einbauen Durchflussrichtung beachten spannungs und biegemomentfrei einbauen 8 Inbetriebnahme 8 1 Hinterdruck einstellen 1 Absperrarmatur eingangsseitig schließen 2 Ausgangsseite druckentlasten z B durch Wasser zapfen 3 Absperrarmatur ausgangsseitig schließen 4 Schlitzschraube lösen Schlitzschraube...

Page 4: ...bsperrarmatur eingangsseitig schließen 2 Ausgangsseite druckentlasten z B durch Wasser zapfen 3 Absperrarmatur ausgangsseitig schließen 4 Manometer montieren 5 Schlitzschraube lösen Schlitzschraube nicht herausdrehen 6 Absperrarmatur eingangsseitig langsam öffnen 7 Gewünschten Hinterdruck einstellen z B 4 bar 8 Skalenwert z B 4 mit Markierung in Fenstermitte in Übereinstimmung bringen 9 Schlitzsch...

Page 5: ...derer austauschen Kein oder zu wenig Wasserdruck Absperrarmaturen vor oder hinter der Sicherheitsgruppe nicht ganz geöffnet Absperrarmaturen ganz öffnen Sicherheitsgruppe nicht in Durchflussrich tung montiert Sicherheitsgruppe in Durchflussrichtung montieren Pfeilrichtung auf Gehäuse beachten nur SG150D Wasseraustritt aus Federhaube Membrane Ventileinsatz defekt Ventileinsatz ersetzen Kein oder zu...

Page 6: ...1 2AB 3 4 A152 3 4AB 10 bar 1 2 A152 1 2AC 3 4 A152 3 4AC gültige Prüfnummer 2 Verschlussstopfen mit O Ring R1 4 5 Stück S06K 1 4 3 Ablauftrichter TA160S 4 Einsteckrückfluss 1 2 2166200 verhinderer 3 4 2110200 5 Dichtringsatz 1 2 0901443 10 Stück 3 4 0901444 6 Federhaubekomplettmit Einstellskala 1 2 3 4 0901515 7 Ventileinsatz komplett ohne Sieb 1 2 3 4 D06FA 1 2 8 Ersatzsieb 1 2 3 4 ES06F 1 2A 9 ...

Page 7: ... Set Mit Löttülle M08M für SG150 D150 D160S VST06 A VST06 B FN09S HABEDO Nachrüstfilter Rückspülbarer Feinfilter zum nachträglichen Umrüsten des Druckminderers zur Filterkombination M07M Manometer Gehäuse 63 mm Anschlusszapfen hinten G1 4 Teilung 0 4 bar 0 10 bar 0 16 bar 0 25 bar Bei Bestellung Teilungs Endwert angeben M08M Manometer Gehäuse 50 mm Anschlusszapfen oben G1 4 Teilung 0 16 bar ZR06K ...

Page 8: ...heck valve to be checked and serviced 3 Application For closed hot water storage units up to 200 litres according to DIN 4753 Part 1 and DIN 1988 Tested to TRD 721 for 1 0 to 10 0 bar pressure range 4 Technical data 5 Scope of delivery The safety group comprises Housing with test socket G 1 4 Connections versions AA AB and AC Shutoff valve Complete pressure reducer only with SG150D with fine scree...

Page 9: ...ted The discharge line must be installed with an incline 7 2 Assembly instructions 1 Blow out or rinse pipe line out well 2 Install safety group in the cold water line Note flow direction Install without tension or bending stresses 8 Start up 8 1 Setting outlet pressure 1 Close shutoff valve on inlet 2 Release pressure on outlet side e g through water tap 3 Close shutoff valve on outlet 4 Loosen s...

Page 10: ...utlet pressure e g 4 bar 8 Align scale e g 4 in middle of viewing window 9 Retighten slotted screw 10 Slowly open shutoff valve on outlet 9 4 Cleaning If necessary the filter bowl and the filter can be cleaned 1 Close shutoff valve on inlet 2 Release pressure on outlet side e g through water tap 3 Close shutoff valve on outlet 4 Unscrew filter bowl Use double ring wrench ZR06K 5 Remove filter clea...

Page 11: ...0D only Water is escaping from the spring bonnet Diaphragm in valve insert is faulty Replace valve insert Too little or no water pressure Pressure reducing valve is not set to the desired outlet pressure Set outlet pressure Filter in pressure reducing valve is conta minated Clean or replace filter The outlet pressure set does not remain constant Filter in pressure reducing valve is conta minated o...

Page 12: ... 1 2AB 3 4 A152 3 4AB 10 bar 1 2 A152 1 2AC 3 4 A152 3 4AC valid approval No 2 Blanking plug with O ring R1 4 5 pcs S06K 1 4 3 Discharge tundish TA160S 4 Check valve insert 1 2 2166200 3 4 2110200 5 Sealing ring 1 2 0901443 10 pcs 3 4 0901444 6 Spring bonnet complete with setting scale 1 2 3 4 0901515 7 Valve insert complete without filter 1 2 3 4 D06FA 1 2 8 Replacement filter 1 2 3 4 ES06F 1 2A ...

Page 13: ...er connections M08M für SG150 D150 D160S VST06 A VST06 B FN09S HABEDO Retrofit filter Reverse rinsing filter for retro conversion to a filter combination unit of pressure reducing valves M07M Pressure gauge Housing diameter 63 mm rear connection thread G1 4 Ranges 0 4 0 10 0 16 or 0 25 bar Please indicate upper value of pressure range when ordering M08M Pressure gauge Housing 50 mm connecting pin ...

Page 14: ...s est une soupape à action directe C est à dire qu une force méca nique un ressort s oppose à la force d ouverture Les robinets d arrêt servent à tester les clapets d arrêt de non retour et à leur maintenance 3 Mise en oeuvre Für geschlossene Wassererwärmer bis 200 l nach DIN 4753 Teil 1 und DIN 1988 Pièce certifié conforme à la norme de construction TRD 721 pour la plage de pression 1 10 bar 4 Ca...

Page 15: ...pente 7 2 Instructions de montage 1 Bien purger ou rincer la tuyauterie 2 Installer la vanne de sécurité combinée Vérifier le sens de passage du fluide Vérifier l absence de contraintes anormales en traction et en flexion 8 Mise en service 8 1 Réglage de la pression de sortie 1 Fermer le robinet d isolement en amont 2 Dépressuriser le côté sortie par ex en ouvrant la vanne de purge etc 3 Fermer le...

Page 16: ...e 1 Fermer le robinet d isolement en amont 2 Dépressuriser le côté sortie par ex en ouvrant la vanne de purge etc 3 Fermer le robinet d isolement en aval 4 Monter le manomètre 5 Desserrer la vis à fente Ne pas retirer cette vis 6 Ouvrir lentement le robinet d isolement en amont 7 Régler la pression à la valeur souhaitée p e 4 bar 8 Faire correspondre la valeur de l échelle avec le point de répère ...

Page 17: ...suffisante ou nulle les vannes d isolement avant ou après la vanne ne sont pas ouverts complètement Ouvrir complètement les vannes d isolement Vanne de sécurité combinée pas installé dans le sens de l écoulement Installer la vanne dans le sens de l écoulement SG150D seulement Sortie d eau au niveau de la coiffe du ressort Membrane défectueuse dans l ensemble soupape de vanne Remplacer l ensemble g...

Page 18: ... 2AB 3 4 A152 3 4AB 10 bar 1 2 A152 1 2AC 3 4 A152 3 4AC Numéro de contrôle valable 2 Bouchon de fermeture avec joint torique R1 4 5 pièces S06K 1 4 3 Cône d écoulement TA160S 4 Dispositif anti reflux à emboîter 1 2 2166200 3 4 2110200 5 Joints d étanchéité 1 2 0901443 quantité 10 3 4 0901444 6 Ensemble complet 1 2 3 4 0901515 7 Jeu de rechange complet sans tamis filtrant 1 2 3 4 D06FA 1 2 8 Eléme...

Page 19: ...ord Avec douille à souder M08M für SG150 D150 D160S VST06 A VST06 B FN09S HABEDO Filtre de rechange Filtre fin à rinçage à contre courant pour montage ultérieur sur un détendeur D06F à partir de la série 1977 pour combinaison de filtres M07M Manomètre Boitier 63 mm raccord arrière G1 4 Echelles 0 4 0 10 0 16 0 25 bar M08M Manometer Gehäuse 50 mm Anschlusszapfen oben G1 4 Teilung 0 16 bar ZR06K Clé...

Page 20: ...che una forza meccanica molla agisce contro una forza di apertura La valvola di chiusura serve per controllare la valvola anti riflusso 3 Uso Per dispositivi di riscaldamento acqua chiusi fino a 200 l secondo DIN 4753 parte 1 e DIN 1988 Pezzo esaminato secondo TRD 721 per il campo di pressione 1 10 bar 4 Dati tecnici 5 Fornitura Il gruppo di sicurezza si compone di Corpo con raccordo di controllo ...

Page 21: ...cquare bene la tubazione 2 Montare il gruppo di sicurezza nella condotta dell acqua fredda Rispettare la direzione del flusso senza tensione e momento flettente 8 Messa in servizio 8 1 Regolazione della pressione a valle 1 Chiudere il raccordo di blocco sul lato entrata 2 Depressurizzare il lato di uscita per es tramite il rubi netto dell acqua 3 Chiudere il raccordo di blocco sul lato di uscita 4...

Page 22: ...uova regolazione è possibile con l ausilio di un manometro 1 Chiudere il raccordo di blocco sul lato entrata 2 Depressurizzare il lato di uscita per es tramite il rubi netto dell acqua 3 Chiudere il raccordo di blocco sul lato di uscita 4 Montare il manometro 5 Allentare la vite con intaglio Non svitare la vite con intaglio 6 Aprire il raccordo di blocco sul lato di ingresso 7 Registrare la pressi...

Page 23: ...stente Armature di blocco davanti o dietro il gruppo di sicurezza non interamente aperte Aprire completamente i raccordi di blocco Gruppo di sicurezza non montato in dire zione del flusso Montare il gruppo di sicurezza in direzione del flusso osservare la direzione della freccia sulla custodia solo SG150D Fuoriuscita di acqua dalla calotta a molla Membrana nell inserto della valvola difet tosa sos...

Page 24: ...2 1 2AB 3 4 A152 3 4AB 10 bar 1 2 A152 1 2AC 3 4 A152 3 4AC Numero di omologazione valido 2 Tappo di chiusura con guarnizione O ring R1 4 5 pezzi S06K 1 4 3 Imbuto di scarico TA160S 4 Inserto dispositivo anti riflusso 1 2 2166200 3 4 2110200 5 Set anello di tenuta 1 2 0901443 10 pezzi 3 4 0901444 6 Cappello completo 1 2 3 4 0901515 7 Inserto valvola completo senza filtro 1 2 3 4 D06FA 1 2 8 Setacc...

Page 25: ...o filettato VST06 B Kit di allacciamento Con becco saldato M08M für SG150 D150 D160S VST06 A VST06 B FN09S HABEDO Filtro ausiliare Microfiltro lavabile per la modifica successiva per la combinazione del filtro M07M Manometro Alloggiamento da 63 mm rubinetto di collega mento posteriore G 1 4 Divisione 0 4 0 10 0 16 0 25 bar M08M Manometro Corpo 50 mm perno di raccordo sopra G1 4 Divisione 0 16 bar ...

Page 26: ...Honeywell GmbH 26 MU1H 1355GE23 R1012 I ...

Page 27: ...MU1H 1355GE23 R1012 27 Honeywell GmbH I ...

Page 28: ... 49 6261 81309 http ecc emea honeywell com Manufactured for and on behalf of the Environmental and Combustion Controls Division of Honeywell Technologies Sàrl Z A La Pièce 16 1180 Rolle Switzerland by its Authorised Represen tative Honeywell GmbH MU1H 1355GE23 R1012 Subject to change 2012 Honeywell GmbH ...

Page 29: ...MU1H 1355GE23 R1012 Honeywell GmbH 8 1 4 8 5 7 9 2 1 bar 6 8 10 4 2 0 4 5 6 8 7 9 11 10 12 13 bar 6 8 10 4 2 0 9 3 8 9 5 7 4 9 4 6 4 5 ...

Page 30: ...ntenance 9 23 Disposal 10 24 Troubleshooting 11 25 Spare Parts 12 26 Accessories 13 F 1 Consignes de sécurité 14 2 Description fonctionelle 14 3 Mise en oeuvre 14 4 Caractéristiques 14 5 Contenu de la livraison 14 6 Variantes 14 7 Montage 15 8 Mise en service 15 9 Maintenance 15 10 Matériel en fin de vie 17 11 Défaut recherche de panne 17 12 Apercu pièces 18 13 Accessoires 19 I 1 Avvertenze di sic...

Reviews: