4. Series 8 IOTA Pinouts
4.2. Differential Analog input IOTA (Models 8X-TAIDA1 and 8X-TAIDB1)
R500
Series 8 I/O User's Guide
69
April 2017
Honeywell
If TB2
screw is
used
Then, the
channel is
used
The pair of jumper is
short for differential
configuration
The pair of jumper
is short for single
ended
configuration
1
16
J233 - J235
J234 - J235
2
15
J230 - J232
J231 - J232
3
14
J227 - J229
J228 - J229
4
13
J224 - J226
J225 - J226
5
12
J245 - J247
J246 - J247
6
11
J242 - J244
J243 - J244
7
10
J239 - J241
J240 - J241
8
9
J236 - J238
J237 - J238
9
8
J204 - J205
J203 - J205
10
7
J207 - J208
J206 - J208
11
6
J210 - J211
J209 - J211
12
5
J213 - J214
J212 - J214
13
4
J222 - J223
J221 - J223
14
3
J219 - J220
J218 - J220
15
2
J216 - J217
J215 - J217
16
1
J249 - J250
J248 - J250
Terminal Block 2
8X-TAIDB1 IOTA
If TB2 screw
is used
Then, the
channel is
used
The pair of jumper is
short for differential
configuration
The pair of jumper is
short for single
ended configuration
1
16
JP48 - JP50
JP49 - JP50
2
15
JP45 - JP47
JP46 - JP47