5. Series 8 I/O
Configuration Form Reference
5.6. Configuring the Main tab - IOM block
R500
Series 8 I/O User's Guide
113
April 2017
Honeywell
Plain text
Parameter name
User
configurable
Notes
Execution State
IOMSTATE
No
Defines the execution state.
Associated IOLINK
IOLINK
No
Defines the associated
IOLINK.
Database Valid
No
Defines if the database is
valid.
IOM Location
IOPLOCATION
Yes
Identifies the user-entered
location (within the plant)
where this IOM can be
found.
Number of Channels
NUMCHANS
No
The number of channels
available in the IOM.
I/O Link Scan Rate
SCANRATE
Yes
Defines the scan rate.
I/O Link Cable Color
IOLINKCOLOR
No
Defines cable color. See
This IOM is
redundant
IOREDOPT
Yes
Module is part of redundant
pair.
Status
IOMSTSA
No
Defines status of IOM:
Idle, OK, No Response
Operation
IOMOPER
No
Defines operation status of
IOM:
Primary, Secondary
Redundancy Status
REDDATA
No
Defines if redundancy is
enabled.
Frequency 60/50Hz
(TC/RTDonly)
FREQ6050
Yes
User-configured power
supply determination:
50Hz or 60Hz (TC/RTD)
Command
IOMCOMMAND
No
Swap primary, reset errors,
and so on.
Digital Input Mode
DIMODE
Yes
Defines the mode of the
Digital Input 24VDC and
DIGITAL INPUT
SEQUENCE OF EVENTS
modules to be Normal,