13. Series 8 I/O
Alarms and Failures
13.2. Reviewing IOM soft failures
R500
Series 8 I/O User's Guide
277
April 2017
Honeywell
49
F2NOTCAL
FTA2 not calibrated.
Diagnostic check:
Cause:
FTA2 not calibrated
Solution:
50
F1COM_FL
TC/RTD FTA 1 communication failure.
Diagnostic check:
TC/RTD FTA 1 communication failure.
Cause:
TC/RTD FTA 1 communication failure.
Solution:
Check the connection from the Power Adapter to FTA 1. If the
FTA is missing, install the FTA. If the FTA is present, replace
the FTA.
51
F2COM_FL
TC/RTD FTA 2 communication failure.
Diagnostic check:
TC/RTD FTA 2 communication failure 2.
Cause:
TC/RTD FTA 2 communication failure.
Solution:
Check the connection from the Power Adapter to FTA 2. If the
FTA is missing, install the FTA. If the FTA is present, replace
the FTA.
52
F1_IDERR
TC/RTD FTA 1 identification failure.
Diagnostic check:
TC/RTD FTA 1 identification failure.
Cause:
TC/RTD FTA 1 identification failure.
Solution:
Verify/correct the FTA pinning.
53
F2_IDERR
TC/RTD FTA 2 identification failure