4. Series 8 IOTA Pinouts
4.2. Differential Analog input IOTA (Models 8X-TAIDA1 and 8X-TAIDB1)
R500
Series 8 I/O User's Guide
63
April 2017
Honeywell
Custom wiring scenarios
by cutting the jumper (for example, JP1). Configure the jumper settings as single-
ended according to the
Table 15 Series 8 differential Analog Input 9 inch and 12 inch
Note:
You must plan cautiously when you cut the JP1 to JP16 jumpers as they are
non-repairable. That is, once these jumpers are cut, you cannot short these jumpers.
Voltage input (Device ground)
Voltage output transducer is connected across TB1-2 and TB2-16 as illustrated in the
following figure. To use voltage output transducer, disconnect the
250Ω spool resistor
by cutting the jumper (for example, JP1). Configure the jumper settings for differential
configuration according to the
Table 15 Series 8 differential Analog Input 9 inch and 12