Sensepoint XCD Technical Manual SPXCDHMANEN Issue 2
20
7 Default configuration
The Sensepoint XCD transmitter is supplied with the following default configuration.
Function
Value/Setting
Meaning
Sensor Type
Automatic according to Sensor type
connected
XCD recognizes the XCD sensor cartridge according
to the gas type within its own sensor family i.e. mV,
EC or O
2
.
Signal output
≥0.0<1.0 mA
Fault (refer to table 5 section 12.3 for details)
2.0 mA or 4.0 mA (17.4mA)
Inhibit (during configuration/user settings)
For Oxygen, 2.0 mA or 17.4 mA
4.0 mA to 20.0 mA
Normal gas measurement
22.0 mA
Maximum over range
Alarm Relay 1*
Value is sensor dependant
Lower alarm level
De-energized
Energizes on alarm
Contact Normally Open (NO)
Closes on alarm
Alarm Relay 2*
Value is sensor dependant
Higher alarm level
De-energized
Energizes on alarm
Contact Normally Open (NO)
Closes on alarm
Fault Relay
<1mA
Detector Fault
Energized
De-energizes on alarm
Contact Normally Open (NO)
Closes on alarm
Inhibit
2.0 mA (default) or 4.0 mA for Toxic
and Flammable
2.0 mA (default) or 17.4 mA
For Oxygen
Signal output inhibited during menu use.
If any relay is set to inhibit relay, then inhibit relay will
be activated.
Timeout
Disabled
No inhibit timeout. The detector waits for a button
press before returning to the previous state/setting.
Timeout period can be set in ‘Configure Inhibit’ menu
in
Configuration Mode
.
Password
0000 (Disabled)
0000 (Password disabled). If changed then password
is activated.
Location
(Tag Number)
0000
Optional feature to identify the location or User’s “Tag”
number of the XCD
Temperature
o
C
Option to have
o
C or
o
F
* Alarm relays automatically reset when reading falls within alarm thresholds. If relay configured to LATCH, then relays must be reset using
the Magnetic Wand.
Table 3: Default configuration
Gas Name
Default Range
Lower Alarm
Lower Alarm
Type
Higher Alarm
Higher Alarm
Type
Oxygen
25.0%VOL
19.5%Vol
Falling
23.5%Vol
Rising
Hydrogen Sulfide
50.0ppm
10.0ppm
Rising
20.0ppm
Rising
Carbon Monoxide
300ppm
100ppm
Rising
200ppm
Rising
Hydrogen
1,000ppm
200ppm
Rising
400ppm
Rising
Flammable IR
100%LEL
20%LEL
Rising
40%LEL
Rising
Flammable CAT
100%LEL
20%LEL
Rising
40%LEL
Rising
Carbon Dioxide IR
2.00%Vol
0.40%Vol
Rising
0.80%Vol
Rising
For details of how to change the configuration of the Sensepoint XCD please refer
to section 13.
Summary of Contents for Sensepoint XCD
Page 1: ...Technical Manual Sensepoint XCD Gas Detector P R E L A U N C H ...
Page 54: ...Sensepoint XCD Technical Manual SPXCDHMANEN Issue 2 54 17 6 Mounting Bracket Drawing ...
Page 56: ...Sensepoint XCD Technical Manual SPXCDHMANEN Issue 2 56 China GB Ex English Version ...
Page 57: ...Sensepoint XCD Technical Manual SPXCDHMANEN Issue 2 57 China PA Certification ...
Page 58: ...Sensepoint XCD Technical Manual SPXCDHMANEN Issue 2 58 18 2 Korea KTL ...
Page 60: ...Sensepoint XCD Technical Manual SPXCDHMANEN Issue 2 60 ATEX for Sensor ...
Page 62: ...Sensepoint XCD Technical Manual SPXCDHMANEN Issue 2 62 IEC Ex for Sensor ...