Sensepoint XCD Technical Manual SPXCDHMANEN Issue 2
35
13 Menu’s and Advanced Configuration
13.1 Abort Function
In Review Mode or Configuration Mode the user can escape one step back from the
current position using the Abort Function. To do this the user must activate the Enter
switch for more than 3 seconds with the Magnetic Wand. Switching between each pair of
modes or between menus and sub menus are shown in the following table.
From
To
Example
Review Mode
Monitoring Mode
Activate Enter switch for more than 3 seconds
while in Review Mode
Configuration Mode
Monitoring Mode
Activate Enter switch for more than 3 seconds
while navigating menus in the Configuration
Mode
Configuration Mode
sub menu
Configuration
Mode main menu
Activate Enter switch for more than 3 seconds
while in a sub menu
Table 6: Transmitter menu switching
13.2 Configuration Mode
The table below shows the functions available via the configuration menu that can be
displayed on the transmitter and accessed using the Magnetic Wand.
The instrument will show the main Menu when the “Enter” switch is activated with the
Magnetic Wand and held for at least 3 seconds.
The Menu is password protected to prevent any unauthorized changes. The password is
initially disabled and the default password is ‘0000’. If the default password is changed
to other than ‘0000’, then the password is enabled automatically and requested when
entering Configuration Mode.
With the Menu showing, the following functions can be performed: calibration, bump test,
sensor selection and configuration of parameters such as measuring range, calibration
gas level, calibration interval, inhibit current, inhibit timeout, alarm setting, relay setting,
password change, location setting, temperature unit reading, force analogue output and
alarm function checks.
While in Configuration mode, the output current of the transmitter is inhibited to prevent
false alarms.
Names, displays and descriptions for each menu item in Configuration Mode are shown in
the following table.
Summary of Contents for Sensepoint XCD
Page 1: ...Technical Manual Sensepoint XCD Gas Detector P R E L A U N C H ...
Page 54: ...Sensepoint XCD Technical Manual SPXCDHMANEN Issue 2 54 17 6 Mounting Bracket Drawing ...
Page 56: ...Sensepoint XCD Technical Manual SPXCDHMANEN Issue 2 56 China GB Ex English Version ...
Page 57: ...Sensepoint XCD Technical Manual SPXCDHMANEN Issue 2 57 China PA Certification ...
Page 58: ...Sensepoint XCD Technical Manual SPXCDHMANEN Issue 2 58 18 2 Korea KTL ...
Page 60: ...Sensepoint XCD Technical Manual SPXCDHMANEN Issue 2 60 ATEX for Sensor ...
Page 62: ...Sensepoint XCD Technical Manual SPXCDHMANEN Issue 2 62 IEC Ex for Sensor ...