EXCEL 10 HAND HELD TOOL
Page 33
74-2566
Select the Frequency Select menu item from the PARAMETERS Main Menu and then press the Enter key to display the
following FREQUENCY SELECT screen.
F R E Q U E N C Y S E L E C T
6 0 H z
5 0 H z
The operator selects between 60 Hz or 50 Hz operation by using the Up/Down Arrow keys to select the appropriate frequency
and then presses the Enter key. The operator has to press the Prev Menu key to get back to the PARAMETERS Main Menu.
Damper Rotation
Select the Damper Rotation menu item from the PARAMETERS Main Menu and then press the Enter key to display the
following DAMPER ROTATION screen.
D A M P E R R O T A T I O N
O p e n = O p e n
O p e n = C l o s e
The operator selects which direction (direct Open = Open or reverse Open = Close acting) the damper motor should be
driven for the damper to fully open. Use the Up/Down Arrow keys to select the appropriate direction and then press the Enter
key. The operator has to press the Prev Menu key to get back to the PARAMETERS Main Menu.
Bypass Duration
Select the Bypass Duration menu item from the PARAMETERS Main Menu and then press the Enter key to display the
following BYPASS DURATION screen.
B Y P A S S D U R A T I O N
< m i n u t e s >
The HHT displays the current value for BYPASS DURATION in <minutes> (the range is 0 through 1080 with a default of 180
minutes). The operator enters a new value for the BYPASS DURATION and then presses the Enter key. The operator has to
press the Prev Menu key to get back to the PARAMETERS Main Menu. If the value entered by the operator is not between or
including the values of 0 and 1080, the HHT beeps and displays the following error message Error, Out Of Range. The
operator must press the Prev Menu key to get back to the previous screen that allows a new value to be entered.
B Y P A S S D U R A T I O N
Error, Out Of Range