EXCEL 10 HAND HELD TOOL
95-2566
14
Standby Heat:
67
°
F (19.4
°
C)
Unoccupied Heat:
55
°
F (12.8
°
C)
NOTES: If a controller is configured for a wall module with a setpoint adjustment, the Occupied Heating and Cooling
Setpoints are disabled and the Heat/Cool Deadband is enabled. The Standby Heating and Cooling Setpoints are
Used at this Point to also calculate Heating and Cooling Setpoint Limits.
If a controller has no wall module setpoint adjustment configured, the Occupied Heating and Cooling Setpoints are
enabled and the Heat/Cool Deadband is disabled.
If a controller is configured to share a wall module that is wired to another controller, all temperature setpoints are
disabled.
If a controller is configured for pressure independent flow tracking, all temperature setpoints and flow setpoints are
disabled.
The HHT will not prevent the operator from entering values into disabled setpoints but the controller will ignore them.
The operator can either press the Prev Menu key to go back to the previous menu and display another setpoint or press the
Prev Menu key twice to go back to the I/O POINTS menu.
Diagnostic Points
Select the Diagnostic Points menu item using the Up/Down Arrow keys and then press the Enter key. Under the
Diagnostic Points heading the operator is able to display the current value of the points listed in the Diagnostic Points table
shown below, see Table 6. These points are display only and can be displayed at any operator level.
Table 6. Diagnostic Points.
HHT Point Name
R/W Read Write or R/O Read Only
Write Access Level
Input/ Output
Scheduled Occupancy
R/O
None
Output
Network Occupancy
R/O
None
Output
Button Occupancy
R/O
None
Output
Occupancy Sensor
R/O
None
Output
Setpoint Reset
R/O
None
Input
DLC Shed
R/O
None
Output
Select the Scheduled Occupancy from the list of points under the Diagnostic Points menu and then press the Enter key to
display the value or state. The following screen displays the Scheduled Occupancy state.
S c h e d u l e d O c c u p a n c y
State is Un_Occ
The operator can either press the Prev Menu key to go back to the previous menu and display another diagnostic point or
press the Prev Menu key twice to go back to the I/O POINTS menu.
Commandable Points
Select the Commandable Points menu item using the Up/Down Arrow keys and then press the Enter key. Under the
Commandable Points heading the operator is able to display the current value or state of the points listed in the
Commandable Points table shown below, see Table 7. This table shows that the operator has to be logged on as a level 3
operator in order to modify the values/states. If the operator is logged onto a level less than a level 3, then the screen displays
only the value and engineering unit (as shown in a previous screen view for the Room Temp) or the state (as shown in the
previous screen view for the Scheduled Occupancy).