W4995B_DE_1204     Seite 7/8

PEHA Lichtsteuerung  –  PEHA Elektro GmbH & Co. KG a Honeywell Company · Gartenstraße 49 · 58511 Lüdenscheid · Deutschland · www.peha.de · [email protected]

„One Switch“ Dimming

OneSwitch dimming affords local control to the end-user whereby 
a simple, momentary, push-to-make wallswitch can be used to 
raise or lower the lighting level or to toggle the output ON/OFF. A 
short press of the switch (less than 1 second) will toggle the out-

put status while a longer press will raise or lower the output. Each 
time the switch is pressed, the direction of dimming reverses. If the 
switch has not been pressed for 5 seconds, the direction will be up 

(brighter) - unless the output is already above 90% in which case 

the direction is down. If the switch is held continuously, and the 
output reaches maximum, the light output will remain at this level 
until the switch is released - a latching switch may be connected 
in parallel allowing the occupancy detection to be overridden on 

(Note: If the initial direction was down, when the output reaches 

minimum it will ramp back up automatically).

Setting the Regulating Photocell

This product is intended for use with high frequency regulating 

ballasts with digital control inputs. An infrared programming tool, 
the D HP2000, is required for programming the regulating light 
level set point. 
Using the D HP2000 Programmer, enter the Utilities menu and 
select ‘Set Light Level’. Use the ‘up’ and ‘down’ buttons to manually 
adjust the light output from the luminaire(s) and when at the requi-
red level press and hold ‘OK’ to store. The luminaire(s) will blink to 
acknowledge a successful store operation.

Commissioning

The factory default settings shown in the table below will be 

appropriate for most applications. However, the installer does have 
the facility to re-programme all parameters using the D HP2000 
Programmer. These parameters may be reprogrammed any number 
of times and all settings will be retained in the event of a power loss.

Lens Mask

A lens mask (D HBPIRLM) is available to mask end-of-aisle move-

ment from being detected.

Important Additional Notes

1. All terminals on this product are provided for final connections. 

It is not intended that the product be used as a junction box for 
looping cables.

2. Although nominally 12V, the dimming output is not ELV and 

therefore should be treated with the same respect as mains with 
regard to wiring practice. The 0V line of the dimming output is 
almost at Neutral potential.

3. The dimming control output should be connected only to the 

control input of the ballasts - never to other detectors.

4. Due to the fact that the photocell is on the ceiling looking down, 

it is not possible for measurements made with a lux meter on 
the working plane to remain constant when daylight illuminates 
the ceiling and the working plane to a differing extent. Therefore, 
products of this type should be regarded as capable of maintai-
ning an APPROXIMATE light level only.

GB

Parameter

Options (Pre-set)

Power up

On

 / Off

Sets the luminaire state at power up irrespective of occupancy. Useful in reducing 
start-up load following power cut. Power-Up off - responds to occupancy after 30 
seconds.

Response

Auto

 / Manual/Bus / Manual Only

If set to Auto, the presence detector switches the luminaire on and off automatically. 
If set to Manual Only it can only be turned on using OneSwitch or the hand-held 
controller. If set to Manual/Bus, an MLS Bus turn on command for a Zone to which 
the detector belongs will also bring the lights on. In all modes the „ When Vacant“ 
behaviour (see below) is initiated automatically.

Off Delay

1 min – 96 hours, disabled / 

10 min.

The time for which the luminaire will stay in the Occupied state following the last 
detected movement. There is also a 10 second setting for walk-testing.

24 hour cycle

On / 

Off 

Output turns off for duration of ‘Off delay’ if area is unoccupied for 24 hours.

Bus Connect

Yes

 / No

Do/Do not Signal/Receive on MLS Bus.

1st Zone
2nd Zone 
3rd Zone 
4th Zone

1-100, (Zone #) 

Individual Zones influencing and being influenced by this Detector.

Corridor 1
Corridor 2

1-100, 1-100 (Zone Span) 

Ranges of Zones influencing, but not influenced by this Detector.

Global 1 Rx 
Global 2 Rx

Yes / 

No

 

Respond to Selective Load Shedding

Manual Input

Shared / 

Local

Do /Do not signal OneSwitch commands on the MLS Bus.

Start Lamps

Max

 / Min

Strike lamps at highest / lowest output.

Entry scene

Scene 1-6 / 

Scene 1

Sets which scene is recalled when an unoccupied area is entered.

Bright-Out

Yes / 

No

If set to Yes, movement fails to refresh the off delay if the ambient light level exceeds 
125% of the set level, and the luminaire will switch off when the Off Delay has 
elapsed. (Note Dimming must be set to 100%)

Fade to Off

Yes / 

No

When no presence is detected, and after the off delay period, the lamps can fade out 
instead of switching off (approx 80 seconds to fade from100% to 0%).

When Vacant

off

 / min / reg <25% / Scene 6

Options for a vacant area after the Off Delay has timed out. Luminaires can turn off, 
remain at minimum output, regulate with a 25% output limit, or goto the set Scene 
6 level until the next period of occupancy. If programmed to remain at minimum, 
regulate below 25%, or go to Scene 6 there are further programmable options to 
switch off after three times the Off Delay (XTN) or when no further movement has 
been detected anywhere in the building (BLD).

Photocell

Reg 100-50% / Passive / Active / Disabled

Reg 100%

Sets the regulating range of the ballast in daylight conditions, i.e. at 100% the ballast 
can regulate over its full range, at 70% the ballast will not dim below 30% output. 
Manual override is not affected.

Lamp Max

10 – 100 % (10-50% in 5 % steps, 50-100% in 10 % steps)  

100 %

Control output upper limit (10 - 50% in 5% increments; 50%+ in 10% increments) 
Manual override is not affected.

Lower Threshold

0-

254

Point at which photocell allows lights to switch on.

Upper Threshold

0-

254

 

Point where photocell turns lights off if Photocell is in Active mode.

Summary of Contents for PEHA MLS Digital Hi-Bay D MLS2001AHBF

Page 1: ...ny Gartenstraße 49 58511 Lüdenscheid Deutschland www peha de peha peha de D MLS2001AHBF D MLS2001AHBSM PEHA Lichtsteuerung MLS Digital MLS Digital Hi Bay D MLS2001AHBF D MLS2001AHBSM D Installations und Inbetriebnahmeanleitung Seite 2 GB Installation and Commissioning Instructions Page 6 ...

Page 2: ...it dieser Regelkreis korrekt funktioniert muss die Fotozelle gute Sicht auf das reflektierte Licht nur von der Leuchte den Leuchten haben die sie steuert steuern NICHT auf benachbarte Leuchten die nicht unter ihrer Regelung stehen Je höher also die Präsenzmelder montiert sind desto weiter müssen sie voneinander entfernt sein um sicherzu stellen dass sie hauptsächlich ihr eigenes Licht sehen Deshal...

Page 3: ...odi wird das When vacant Verhalten siehe unten automatisch gestartet Off Delay Nachlaufzeit 1 Min 96 Stunden deaktiviert 10 min Gibt die Nachlaufzeit nach der letzten erkannten Bewegung bis zum Ausschalten der Beleuchtung an Wird innerhalb dieser Zeit eine erneute Bewegung festgestellt startet die Nachlaufzeit erneut Im walk test Modus Geh Test ist die Nachlaufzeit 10 sec 24 hour cycle 24 Std Zykl...

Page 4: ...zung zur Folge haben Alle Arbeiten am Versorgungsnetz und Gerät dürfen nur von autorisierten Elektrofachkräften durchgeführt werden Gerät spannungsfrei schalten Gerät gegen Wiedereinschalten sichern Gerät auf Spannungsfreiheit überprüfen Vor dem Einschalten Gehäuse fest verschließen Das Gerät ist nur für die bestimmungsgemäße Verwendung vorgesehen Ein eigenmächtiger Umbau oder eine Veränderung ist...

Page 5: ...pfohlen Schaltvermögen 6A Ausgang 1 10V Analog max 25 Vorschaltgeräte Fotozelle Einstellbar von 50 5000 lux via D HP2000 Nachlaufzeit 1 Minute 96 Stunden einstellbar und 10 Sekunden Geh Test Modus Gewicht ca 200 g Farbe weiß Material PC ABS schwer entflammbar Schutzart IP3X D Flange 10mm deep 100mm 62mm deep OneSwitch Live Neutral 1 10V Output MLS Bus Connection Polarity free Volt free Output h d ...

Page 6: ...e a closed feedback loop is formed by the luminaire the reflective surface beneath and the photocell For this control loop to function correctly the photocell must have a good view of the reflected light only from the luminaire s under its control NOT from adjacent luminaires not under its control This means that the higher the detectors are mounted the further apart they must be in order to ensur...

Page 7: ...is type should be regarded as capable of maintai ning an APPROXIMATE light level only GB Parameter Options Pre set Power up On Off Sets the luminaire state at power up irrespective of occupancy Useful in reducing start up load following power cut Power Up off responds to occupancy after 30 seconds Response Auto Manual Bus Manual Only If set to Auto the presence detector switches the luminaire on a...

Page 8: ...e national and international regulations Nevertheless if a product should exhibit a defect PEHA warrants to make remedy as follows regardless of any claims against the dealer to which the end user may be entitled as a result of the sales transaction In the event of a justified and properly established claim PEHA shall exercise its prerogative to either repair or replace the defective device Furthe...