78
RP-2002 Series Manual —
P/N 53039:E6 1/26/2017
Programming
Maintenance Programming Level
The History feature allows the operator to view control panel events which have been stored in a
history file in memory and erase the contents of the history file.
Pressing
1
while viewing the History screen will cause the following screen to be displayed:
To view all the events which have occurred in the control panel since the history file was last
erased, press
1
while viewing the Events screen. To view only alarms which have occurred, press
2
while viewing the Events screen. To view events other than alarms, press
3
. The most recent event
will be displayed on the screen. To view all of the selected events, press the up or down arrow keys
to scroll through the list of events. If no events have occurred, the display will read
NO EVENTS IN
HISTORY
.
Pressing
2
while viewing the History Screen will cause the following screen to be displayed:
Pressing
1
while viewing the Erase History Screen will erase all events from the History file. The
display will then return to the History Screen. Pressing
2
will cause the display to return to the
History Screen without erasing the History file.
3.6.3 Walktest
To perform a walktest, press
3
while viewing Maintenance Screen #1. The following screen will be
displayed:
The operator can press
1
to perform a silent walktest or
2
to perform an audible walktest. The
display will read
UNIT IN WALKTEST
. To end the Walktest, press the
Esc
(Escape) key.
Pressing
3
after the walktest has been completed, will allow the operator to view the results of the
walktest.
3.6.4 Time-Date
To program the time and date into the control panel, press
1
while viewing Maintenance Screen #2.
The following display will appear:
To change the time, press
1
to display the following screen:
HISTORY
1=VIEW ALL
2=VIEW ALARMS
3=VIEW OTHER EVENTS
ERASE HISTORY
PROCEED ?
1=YES 2=NO
Erase History Screen
PROGRAMMING
1=INPUT ZONES
2=HISTORY
3=WALKTEST
Maintenance Screen #1
WALKTEST
1=SILENT
2=AUDIBLE
3=VIEW EVENTS
Walktest Screen
PROGRAMMING
1=TIME-DATE
Maintenance Screen #2
TIME AND DATE
1=TIME 01:00A
2=DATE 09212014
3=CLOCK FORM 12HRS
Time and Date Screen
ENTER TIME AS 12HRS
:
01:00
1=AM 2=PM
Time Screen
Summary of Contents for NOTIFIER RP-2002C
Page 158: ...Cut along dotted line ...