74
RP-2002 Series Manual —
P/N 53039:E6 1/26/2017
Programming
Master Programming Level
To program any of the N-ANN-RLY relays, while viewing the appropriate ANN-RLY Option
screen, press the number key corresponding to the relay to be programmed. The following screen
will appear:
Pressing
1
will display the available relay types. Following is a list of the available programming
options for each relay:
• General Alarm
• General Trouble
• General Supervisory
• General Pre-Discharge
• Pre-Discharge Release 1
• Pre-Discharge Release 2
• General Discharge
• Discharge Release 1
• Discharge Release 2
• AC Loss
• Waterflow Delay
• General Abort Release
• Abort Release Release 1
• Abort Release Release 2
• Future Use
• Future Use
• Future Use
• Input Zone 1
• Input Zone 2
• Input Zone 3
• Input Zone 4
• Input Zone 5
• Input Zone 6
Press
2
to select Latching or non-Latching relay. Each press of the 2 key will cause the display to
toggle between
Latching Yes
and
No
.
3.5.8 History
The History option allows an authorized user to view or erase events which have occurred in the
control panel. Pressing
2
while viewing Programming Screen #3 will display the History options as
shown in the following display:
ANN-RLY #
1=TYPE
2=LATCHING NO
PROGRAMMING
1=ANN-BUS
2=HISTORY
3=WALKTEST
Programming Screen #3
HISTORY
1=VIEW EVENTS
2=ERASE HISTORY
History Screen