
RP-2002 Series Manual —
P/N 53039:E6 1/26/2017
129
Template 10: Dual Hazard - Single Detector
FACP Configuration Templates
FACP Operation
•
Input Zone 1 (2-Wire Smoke) Activation only:
Output 1 (Release Circuit 1) will perform an agent release following a 30 second Pre-
Discharge delay and remains on until panel reset.
Output 3 (Release Stage Coded) will pulse 1/2 second on, 1/2 second off until discharge, then
on steady.
•
Input Zone 2 (2-Wire Smoke) Activation only:
Output 1 (Release Circuit 1) will perform an agent release following a 30 second Pre-
Discharge delay and remains on until panel reset.
Output 3 (Release Stage Coded) will pulse 1/2 second on, 1/2 second off until discharge, then
on steady.
•
Input Zone 3 (Manual Release) Activation only:
Output 1 (Release Circuit 1) agent release remains on until reset.
Output 3 (Release Stage Coded) will turn on steady.
•
Input Zone 3 (Abort Release Switch) Activation only:
Pre-Discharge Timer for Release Circuit 1will continue to count down until it reaches 10
seconds and then stop. Releasing the Abort Release Switch will allow the Pre-Discharge Timer
to continue its count down from 10 second. If the Abort Release Switch is again activated
before the Pre-Discharge Timer reaches 0, the Timer will reset to 10 seconds and hold.
•
Input Zone 4 (2-Wire Smoke) Activation only:
Output 2 (Release Circuit 2) will perform an agent release following a 30 second Pre-
Discharge delay and remains on until panel reset.
Output 4 (Release Stage Coded) will pulse 1/2 second on, 1/2 second off until discharge, then
on steady.
•
Input Zone 5 (2-Wire Smoke) Activation only:
Output 2 (Release Circuit 2) will perform an agent release following a 30 second Pre-
Discharge delay and remains on until panel reset.
Output 4 (Release Stage Coded) will pulse 1/2 second on, 1/2 second off until discharge, then
on steady.
•
Input Zone 6 (Manual Release) Activation only:
Output 2 (Release Circuit 2) agent release remains on until reset.
Output 4 (Release Stage Coded) will turn on steady.
•
Input Zone 6 (Abort Release Switch) Activation only:
Pre-Discharge Timer for Release Circuit 2 will continue to count down until it reaches 10
seconds and then stop. Releasing the Abort Release Switch will allow the Pre-Discharge Timer
to continue its count down from 10 second. If the Abort Release Switch is again activated
before the Pre-Discharge Timer reaches 0, the Timer will reset to 10 seconds and hold.
FACP Relay Operation
The following description of FACP relay operations are in addition to normal system operation.
•
Alarm Relay (Latching) - activation of Input Zone 1 (2-Wire Smoke) or Zone 2 (2-Wire
Smoke) or Zone 3 (Manual Release) or Zone 4 (2-Wire Smoke) or Zone 5 (2-Wire Smoke) or
Zone 6 (Manual Release) will operate Alarm Relay
•
Trouble Relay (Tracking) - any system trouble will activate the Trouble Relay
•
Supervisory (Tracking) - the disabling of Releasing Circuit or any other system supervisory
will operate the Supervisory Relay
Summary of Contents for NOTIFIER RP-2002C
Page 158: ...Cut along dotted line ...