
RP-2002 Series Manual —
P/N 53039:E6 1/26/2017
109
Template 3: Single Hazard - Cross-Zone
FACP Configuration Templates
Device Installation Example for Template 3
Notes:
1.
All End-of-Line Resistors, illustrated in this example, are 4.7K
Ω
, ½ watt (PN: 71252).
2.
All devices are connected as Class B circuits. For details on connecting as Class A circuits,
refer to “N-CAC-5X Class A Converter Module” on page 31.
Output Circuit #2
Alarm NAC
Input Circuit #1
2-Wire Smoke
Input Circuit #3
Manual Release
Input Circuit #4
Abort Switch
Input Circuit #5
Discharge Pressure
Output
Circuit #1
Release
Solenoid 1
Output
Circuit #3
Release
Stage Pre-
Discharge
NAC
Input Circuit
#6
Supervisory
Output
Circuit #4
Release
Stage
Discharge
NAC
Input Circuit #2
2-Wire Smoke
ag
ent
tem
p3
.cd
r
Summary of Contents for NOTIFIER RP-2002C
Page 158: ...Cut along dotted line ...