34
NCD Instruction Manual —
P/N LS10210-051NF-E:C 2/18/2019
Operation
Disabled Point
4.5 Disabled Point
When a system point is dis-
abled it will display as fol-
lows on the NCD:
•
Produces a pulsed
audible sound.
•
Turns on the trouble
Relay.
•
D
ISABLED
appears in
the Header Bar.
•
D
ISABLED
illuminates
in the Alert Bar as a
yellow icon and
indicated device event
count.
•
Illuminates the yellow
off normal LED.
•
Displays
DISABLED
and
specific point
information in the
Screen Area.
•
Displays information
on how to react to the
event in the
Informational Text
Area.
4.5.1 Responding to a Disabled Point
To acknowledge the disabled point and silence the NCD sounder do the following:
•
The Informational Text Area on the screen will indicate step by step what needs to be done to acknowledge and silence the event.
•
Tap on the
ACKNOWLEDGE
touch point located in the Header Bar. The acknowledge touch point will be highlighted in blue. A check
mark will appear next to the acknowledged event.
•
BLOCK
ACKNOWLEDGE
allows for multiple events to be acknowledged at once.
•
Tap on the
SILENCE
touch point located in the Header Bar. The
SILENCE
icon in the Alert Bar will illuminate blue once the NCD is
silenced.
•
Enable the disabled point.
•
Once all the events have been acknowledged the blue highlight indicator will move from the
ACKNOWLEDGE
touch point to the
SILENCE
touch point.
Figure 4.5 Disabled Screen
SIGNALS
SILENCED
CO ALARM
TROUBLE
OTHER
Thu 2/22/18
1:38:06PM
Silence
Reset
DISABLED
DISABLE MON
Thu 02/22/18
1:35:57 PM
NO25L01M023
Step 1 Acknowledge each event. This is secondary text to explain what acknowledging an event means and who should do it.
UNACKNOWLEDGED DISABLES (1)
Ack
SUPERVISORY
Third Floor, Storage Room
FIRE ALARM
DISABLED
DISABLE
1
NOTE:
If an unacknowledged, higher priority event exists, the NCD will retain the indications of the higher priority event, such as the LED,
audible tone, etc. The Trouble Relay, flashing event LED will still react at the time of the event