Section 2: Installation
2.1 Preparing for Installation
Choose a location for the NCD that is clean, dry, and vibration-free with moderate temperature. The area should be readily accessible
with sufficient room to easily install and maintain it. There should be sufficient space for cabinet door(s) to open completely.
Carefully unpack the system and inspect for shipping damage. Count the number of conductors needed for all devices and find the appro-
priate knockouts.
Before installing the fire alarm system, read the following:
•
Review the installation precautions at the front of this manual.
•
Installers should be familiar with the standards and codes specified in Section 1.1 “Standards and Specifications”.
•
All wiring must comply with the National and Local codes for fire alarm systems.
•
Do not draw wiring into the bottom 9 inches (22.86 cm) of the cabinet except when using a separate battery cabinet; this space is for
internal battery installation.
Review installation instructions in Section 2.1 “Installation Checklist”.
2.2 Installation Checklist
The checklist that follows contains references to information included in other manuals; see “Related Documentation” on page 7 for doc-
ument part numbers.
!
WARNING: Risk of irreparable equipment damage
Make sure to install system components in the sequence listed below. Failure to do so can damage the control panel and
other system components.
!
WARNING: Risk of irreparable equipment damage
Wear a static discharge strap on wrist to prevent equipment damage.
!
WARNING: ADJUSTING THE SCREEN BRIGHTNESS GREATER THAN 75% WILL REDUCE THE LIFE OF THE
DISPLAY.
Task
Refer to:
1.
Mount the cabinet backbox to the wall.
Section 2.3 “CAB-4 Series Cabinet”
2.
Attach NCD to dress panel.
Section 2.5 “Dress Plate Mounting”
3.
Attach option boards (e.g. network
communications modules and other devices of the
same size) to chassis and dress plates.
Refer to the Installation document for the specific device and dress plates.
4.
Attach chassis in assembled dress plate to
cabinet.
Section 2.3 “CAB-4 Series Cabinet”
5.
Wire Relays
Figure 2.6
6.
Digital Voice components.
Digital Voice Control Manual,
etc.
7.
Network devices.
Noti•Fire•Net Version 5.0 & Higher Manual, or High-Speed Noti•Fire•Net
Manual and/or Installation document for specific device(s).
8.
Main power supply.
Main Power Supply Manual
BB-100/200 Cabinet Installation Instructions.
9.
Install main power supply and batteries. Run
cables to main and optional power supplies, DC
power outputs, relays, etc.
Applicable system and power supply manuals.
WARNING: DO NOT ACTIVATE POWER AT THIS TIME. DO NOT CONNECT BATTERIES.
10.
Check that all mounting holes are secured to insure a proper Earth Ground connection.
11.
Connect wire shielding to Earth Ground.
12.
Apply AC power to the power supply or the control panel.
Do NOT connect batteries until AC power is checked (see next step).
13.
Check AC power.
Power Supply manual.
14.. Connect the batteries using interconnect cable as described in power supply manual.
15.
Install the dress panels, doors and covers.
CAB-3/CAB-4 Series Cabinet Installation Document.
16.
Program the NCD.
Section 3, “Programming”, on page 20
17.
Field test the system.
Table 2.1 Installation Checklist
Summary of Contents for NOTIFIER NCD
Page 29: ...NCD Instruction Manual P N LS10210 051NF E C 2 18 2019 29 Notes ...
Page 36: ...36 NCD Instruction Manual P N LS10210 051NF E C 2 18 2019 Notes ...
Page 38: ...Cut along dotted line ...
Page 40: ...NOTIFIER 12 Clintonville Road Northford CT 06472 1610 USA 203 484 7161 www notifier com ...