Configuring via WIN-PAK
Adding a New NetAXS™ Panel
NetAXS™ Access Control Unit User’s Guide
,
Document 800-00233, Revision A
3
-
7
7. Click the
Advanced
button to display the Advanced Options screen, and select
the desired advanced options. Note that the Advanced U option is not
supported for the NetAXS panel.
8. Display and complete the Inputs tab. If you are using the NetAXS inputs to
monitor the door status or activate a request to exit, then you must reassign the
interlocks as indicated below. If you are not using panel inputs for door status
or egress, you only need to dissolve the interlocks. Note that if you do not
dissolve the default N-1000-IV interlocks, an error will occur during NetAXS
panel initializations.
All Inputs tab functions are available to NetAXS configuration. However, not
all inputs are available and their default functions have changed. NetAXS
supports inputs 1-14. The default functions are listed below. Their default
values are assumed to be zero, unless otherwise noted. You must change the
interlocking.