
2-42
www.honeywell.com
Configuring via the Web Server
Configuring Other I/O & Groups Tab
2.7 Configuring Other I/O & Groups Tab
The NetAXS™ panel provides up to 14 inputs and eight outputs. Two of the inputs
and four of the outputs are “other” inputs and outputs, because you can use them for
other than door lock/unlock functions. This section explains how to configure these
other inputs, outputs, and groups (for pulse and time zone).
2.7.1 Inputs Tab
This tab enables you to configure inputs 13 (AC Power Fail) and 14 (Panel Tamper)
on Terminal Block 8, and the inputs on downstream MIRO boards daisy-chained to
Terminal Block 10. The downstream inputs are numbered 25-96.
Note:
The NetAXS™ panel supports two MIRO types:
• 32/0 – Provides 32 inputs and no outputs.
• 2/16 – Provides two inputs and 16 outputs.
A NetAXS™ panel supports a maximum of six daisy-chained MIROs – two 32/0 boards
and four 2/16 boards. A MIRO-32/0 module has 32 supervised, four-state inputs that
are limited to 2,200 ohms resistance. The MIRO-2/16 has two supervised inputs and
16 SPDT relay outputs; each input is limited to 2,200 ohms resistance. Each board is
configured with a unique address in the Configuration > System > Downstream
Devices tab (see “
Downstream Devices Tab
“ on page 11).
On panels with internal power supply, the Power Fail input generates an alarm when
primary power is lost as indicated by the power supply. The Panel Tamper input
generates an alarm when the NetAXS™ cabinet has been forced open. The
Downstream inputs are available for general use.
Note:
You can also configure the Power Fail and the Panel Tamper inputs for general
use, if you choose not to wire them for power and tamper detection.
Click
Inputs
to display the Inputs screen. The Power Fail input box appears:
Type
Shows the card type. The card type specifies whether the
card holder is configured as a supervisor (Supr), employee
(Empl), temporary employee (Temp), a VIP (VIP), or a
combination of these types.
Tmp
Indicates (with a check mark) that the card is a temporary
card.
Table 2-9: Cards > Reports Field Descriptions (continued)
Field
Description
Summary of Contents for NetAXS
Page 8: ...viii www honeywell com ...
Page 18: ...1 10 www honeywell com Connecting to the Web Server Reading the Select Panel ...
Page 74: ...2 56 www honeywell com Configuring via the Web Server Configuring Users ...
Page 84: ...3 10 www honeywell com Configuring via WIN PAK Adding a New NetAXS Panel ...
Page 86: ...3 12 www honeywell com Configuring via WIN PAK Adding a New NetAXS Panel ...
Page 100: ...4 14 www honeywell com Monitoring NetAXS Status Monitoring System Status ...