H8908B HUMIDISTAT/H8908C DEHUMIDISTAT

69-1341EF

2

8.

Use the two 1 in. (25 mm) mounting screws to 
secure the base to the wall.

Fig. 2. Positioning mounting template. 

IMPORTANT

Use 18- to 22-gauge wire for proper wiring.

9.

Connect the low voltage wires to the leads on the 
H8908.

10.

Replace the H8908 case.

Duct Mounting

IMPORTANT

When mounting near an elbow area, locate the 
control 6 in. (152 mm) upstream from the elbow 
so the element is exposed to the normal airflow 
(Fig. 3).

Fig. 3. Selecting duct location for control.

1.

Locate the control at least 8 in. (203 mm) upstream 
from the humidifier (or dehumidifier/ventilator sup-
ply) in the return air duct. See Fig. 3.

2.

Apply the duct template to the duct location.

3.

Use the duct template, Fig. 4, to make the opening 
and mounting holes for the H8908.

4.

Remove the H8908 case from the base. See 
Fig. 1.

5.

Position the foam gasket on the H8908 base.

6.

Position the base on the duct with the arrow up.

7.

Use the four 1 in. (25 mm) mounting screws to 
secure the base to the duct.

8.

Connect the low voltage wires to the leads on the 
H8908.

9.

Replace the H8908 case.

IMPORTANT

Use 18- to 22-gauge wire for proper wiring.

Fig. 4. Positioning return air duct template.

M13370

THERMOSTAT
WALLPLATE

MOUNTING
TEMPLATE

MOUNTING 
HOLES (2)

WIRING HOLES FOR MOUNTING ON RIGHT. 
USE LEFT HOLES FOR MOUNTING ON LEFT. 

ALTERNATE LOCATION

RETURN 
AIR

RETURN 
AIR

6 in. (152 mm) 
MINIMUM

15 in. (381 mm) 
MINIMUM

BEST 
LOCATION

RETURN AIR DUCT

M13369

CAUTION

Equipment Damage Hazard.
Be careful when selecting control
location and cutting hole in ductwork.
Do not cut or drill into air conditioning
or electrical accessories.
Do not install control on supply (hot air) ductwork.
To use template:
1. Remove backing and apply template to duct.
2. Cut along template dotted line and drill the

mounting holes.

4X DRILL 7/64 IN. DIAMETER
PERCER 4 X 7/64 PO.

MISE EN GARDE

Risque d'endommager le matériel.
Faire attention au moment de choisir
l'emplacement du régulateur et de percer les
trous dans la gaine.
Ne pas couper ou percer les accessoires
électriques ou de climatisation.
Ne pas installer le régulateur sur la gaine
d'alimentation (air chaud).
Utilisation du gabarit:
1. Retirer l'endos du gabarit et placer le gabarit

sur la gaine.

2. Couper le long de la ligne pointillée du gabarit

et percer les trous de fixation.

DUCT TEMPLATE

GABARIT DE GAINE

M13373

Summary of Contents for H8908B Humidistat

Page 1: ...ext to the T8600 The H8908 can also be mounted at any other convenient location in the living area or equipment room See Fig 1 NOTE The H8908 electrical connections are not shared with the thermostat Fig 1 H8908B Humidistat Wall Mounting IMPORTANT Mount the control in an area with average room temperature and average relative humidity The following mounting instructions are for mounting the H8908 ...

Page 2: ...lace the H8908 case IMPORTANT Use 18 to 22 gauge wire for proper wiring Fig 4 Positioning return air duct template M13370 THERMOSTAT WALLPLATE MOUNTING TEMPLATE MOUNTING HOLES 2 WIRING HOLES FOR MOUNTING ON RIGHT USE LEFT HOLES FOR MOUNTING ON LEFT ALTERNATE LOCATION RETURN AIR RETURN AIR 6 in 152 mm MINIMUM 15 in 381 mm MINIMUM BEST LOCATION RETURN AIR DUCT M13369 CAUTION Equipment Damage Hazard ...

Page 3: ...rols Fig 5 Typical wiring diagram for system with fan interlock Fig 6 Typical wiring diagram for system with 2 speed fan motor Fig 7 Typical wiring diagram of current sensing relay with humidifier Fig 8 Typical wiring diagram of sail switch with humidifier Fig 9 Typical wiring diagram for steam humidifiers 1 1 2 PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED 24 VAC WIRING 2 HUMIDIFIE...

Page 4: ...To reduce the relative humidity reduce the setpoint approximately three percent relative humidity every 24 hours To increase the relative humidity increase the sepoint approximately three percent relative humidity every 24 hours Setpoint Adjustment Set the humidity setpoint according to the prevailing outdoor temperature See Table 1 for recommended settings Table 1 Recommended Humidity Controller ...

Page 5: ...ompris afin de d installer le H8908 près d un T8600 Le H8908 peut également être installé à n importe quel endroit dans la maison ou encore dans une salle d installations techniques Voir Fig 1 REMARQUE Le H8908 et le thermostat ne partagent pas le même câblage Fig 1 Humidistat H8908B Installation au mur IMPORTANT Installer le régulateur dans un endroit où la température et l humidité relative ambi...

Page 6: ... couvercle du H8908 IMPORTANT Utiliser du fil de calibre 18 à 22 pour un raccordement adéquat Fig 4 Positionnement du gabarit de la gaine de reprise MF13370 PLAQUE DE MONTAGE DU THERMOSTAT GABARIT TROUS DE FIXATION 2 TROUS POUR LE RACCORDEMENT ET INSTALLATION À DROITE UTILISER LES TROUS DE GAUCHE POUR UNE INSTALLATION À GAUCHE AUTRE EMPLACEMENT AIR REPRIS AIR REPRIS AU MOINS 152 mm 6 po AU MOINS 3...

Page 7: ...un humidificateur asservi au régulateur du ventilateur Fig 6 Schéma de raccordement type d un système avec un moteur de ventilateur à 2 vitesses Fig 7 Schéma de raccordement type d un relais détecteur de courant et d un humidificateur Fig 8 Schéma de raccordement type d un interrupteur à ailette et d un humidificateur Fig 9 Schéma de raccordement type d humidificateurs à vapeur 1 1 2 ALIMENTATION ...

Page 8: ...midité relative abaisser le point de consigne d environ 3 tous les 24 heures Afin d augmenter l humidité relative hausser le point de consigne de 3 tous les 24 heures Réglage du point de consigne Régler le point de consigne de l humidité selon la température extérieure Consulter le Tableau 1 pour obtenir les réglages recommandés Tableau 1 Réglages recommandés du régulateur d humidité FONCTIONNEMEN...

Reviews: