RE-ALLOCATE
LOOP
NOTE MAP/DEVICE
CONFLICT
** SAFE ADDRESSED LOOPS
EDIT LOOP MAP ON COMMS TOOL
PC TO MATCH THE PANEL’S LOOP
MAP
SELECT DEVICE TO BE DELETED
and DELETE
** SAFE ADDRESSED LOOPS
EDIT LOOP MAP ON PC TO MATCH
THE PRINT OUT FROM THE PANEL
CAN ONLY BE CARRIED OUT USING COMMSTOOL SOFTWARE & PC
RETRIEVE LATEST FILE FROM PANEL
USING COMMSTOOL
On ComsTool.
‘Device Configuration’
CHECK
LOOP MAP
If Adding
device(s) - SAFE
Address them
STOP THE LOOP
*
1) Select the Device that follows the New device.
2) Click the INSERT button
3) Select the Newly inserted device.
4) Modify the Type, Sub-Type and Device Selection
to match the New fitted device.
5) Click the CHANGE button
CHECK LOOP MAP DETAILS IN AREA OF CHANGE.
DEVICES DEFAULT TO SECTOR 1, ZONE 1 etc
THEREFORE THE LABELLING & CONFIGURATION
MUST BE EDITED TO SUIT THE SYSTEM
If removing
device(s) -
remove the SAFE
address(s)
**Loop map edit codes:
0
– conn to panel End 1
251
– conn to panel End 2
252
– conn not available
255
– conn avail but not in
use ie o\cct , not connected
*
For Main Loop/mid-spur insertion follow the instruction.
For insertion on a Spur End connection,
select the t-breaker device preceding the new device
and the CommsTool will ask for confirmation
of the new device location.
SAFE Addressing - Inserting / Deleting Devices
Save the Device Configuration
page then Save The Commissioning
Tool Site File with a new name.
Transmit the new Configuration
to the Panel and Note any
Minor/Major Conflicts
Perform a Functional Test
Important Backup ALL Cards to the NVM
Deleting Device
Inserting Device
WIRE IN NEW DEVICE
or REMOVE DEVICE
Summary of Contents for Gent Compact Plus
Page 1: ...Vigilon Plus Basic Commissioning Training ...
Page 4: ...Vigilon Plus 4 6 Loop Panels ...
Page 16: ...Compact Plus 2 loops ...
Page 21: ...Your Turn Power Up ...
Page 24: ...INFO STATUS CARD Card Status Type in a card number in the range of 0 15 ENTER ...
Page 26: ...Vigilon System Loop Architecture ...
Page 27: ...Main Loop PRESS HARD TO PRESS HARD TO Vigilon System Loop Architecture L1 End 1 L2 End 2 ...
Page 30: ...Soft Addressing ...
Page 36: ...SAFE Addressing ...
Page 44: ...Analogue Detection ...
Page 49: ...Digital Outputs and Analogue Channels On Off low tone Hi tone ...
Page 61: ...Site Information ...
Page 63: ...Labelling ...
Page 67: ...Zones ...
Page 74: ...Condition Code Analysis Subfault Exception BS panel V3 EN54 panel V4 ...
Page 76: ......
Page 93: ... Other Panel Functions ...
Page 105: ...VigInSite ...
Page 112: ...Loop Diagnostic Tool LDT ...
Page 119: ...LDT Earth Fault Earth fault Detected Click to Locate Earth fault The Loop will now reallocate ...
Page 120: ...LDT Earth Fault ...
Page 122: ...LDT Reports cont Extracts from an Engineer report ...
Page 123: ...EN54 Part 23 Overview ...
Page 126: ...Wall Mounted VADs CEILING MOUNTED C 6 16 16m ...