Deleting Device
Inserting Device
Allocate the
loop
Note the Recovery
Failure message
Select the Device to be deleted
and
click the DELETE button.
CAN ONLY BE CARRIED OUT USING COMMSTOOL SOFTWARE & PC
Retrieve the Panel with the Commissioning Tool
Ensure SAFE Addressing is NOT Ticked in Options Page
In ComsTool.
‘Device Configuration’
Check the
Loop Map
If Inserting a device
check its Status
Wire In or Remove the
Device
Transmit the new Configuration
to the Panel and Note any
Minor/Major Conflicts
*
1) Select the Device that follows the New device.
2) Click the INSERT button
3) Select the Newly inserted device.
4) Modify the Type, Sub-Type and Device Selection
to match the New fitted device.
. 5) Click the CHANGE button
Remember Zone and Sector the device
according to the site’s Cause and Effect.
Label the new device
Stop the Loop
Perform a Functional Test
*
For Main Loop/mid-spur insertion follow the instruction.
For insertion on a Spur End connection,
select the t-breaker device preceding the new device
and the CommsTool will ask for confirmation
of the new device location.
Soft Addressing - Inserting / Deleting Devices
Save the Device Configuration
page then Save The Commissioning
Tool Site File with a new name.
Important Backup ALL Cards to the NVM
Summary of Contents for Gent Compact Plus
Page 1: ...Vigilon Plus Basic Commissioning Training ...
Page 4: ...Vigilon Plus 4 6 Loop Panels ...
Page 16: ...Compact Plus 2 loops ...
Page 21: ...Your Turn Power Up ...
Page 24: ...INFO STATUS CARD Card Status Type in a card number in the range of 0 15 ENTER ...
Page 26: ...Vigilon System Loop Architecture ...
Page 27: ...Main Loop PRESS HARD TO PRESS HARD TO Vigilon System Loop Architecture L1 End 1 L2 End 2 ...
Page 30: ...Soft Addressing ...
Page 36: ...SAFE Addressing ...
Page 44: ...Analogue Detection ...
Page 49: ...Digital Outputs and Analogue Channels On Off low tone Hi tone ...
Page 61: ...Site Information ...
Page 63: ...Labelling ...
Page 67: ...Zones ...
Page 74: ...Condition Code Analysis Subfault Exception BS panel V3 EN54 panel V4 ...
Page 76: ......
Page 93: ... Other Panel Functions ...
Page 105: ...VigInSite ...
Page 112: ...Loop Diagnostic Tool LDT ...
Page 119: ...LDT Earth Fault Earth fault Detected Click to Locate Earth fault The Loop will now reallocate ...
Page 120: ...LDT Earth Fault ...
Page 122: ...LDT Reports cont Extracts from an Engineer report ...
Page 123: ...EN54 Part 23 Overview ...
Page 126: ...Wall Mounted VADs CEILING MOUNTED C 6 16 16m ...