How to Factory Default a Panel
1.
Take a Commissioning Tool Retrieval of the panel’s config
2. Unprotect NVM
–
Setup > Protect > NVM Card > Disable > Enter
3. Switch On Freebloks
–
Test Eng > Test > Freeblok > Next > [Controller} > Enter
4. Initialise NVM
–
Test Eng > Card > Init > NVM Card > Enter
5. Switch Off Freebloks
–
Test Eng > Test > Freeblok > Previous > {Off} > Enter
6. Disconnect batteries from PSU
7. Isolate Lithium battery located on MCC or MCB
8. Disconnect USB Commissioning lead from panel
9. Press and release the MCC/MCB reset switch then QUICKLY remove mains supply
10. Leave panel powered down for at least 3 minutes
Summary of Contents for Gent Compact Plus
Page 1: ...Vigilon Plus Basic Commissioning Training ...
Page 4: ...Vigilon Plus 4 6 Loop Panels ...
Page 16: ...Compact Plus 2 loops ...
Page 21: ...Your Turn Power Up ...
Page 24: ...INFO STATUS CARD Card Status Type in a card number in the range of 0 15 ENTER ...
Page 26: ...Vigilon System Loop Architecture ...
Page 27: ...Main Loop PRESS HARD TO PRESS HARD TO Vigilon System Loop Architecture L1 End 1 L2 End 2 ...
Page 30: ...Soft Addressing ...
Page 36: ...SAFE Addressing ...
Page 44: ...Analogue Detection ...
Page 49: ...Digital Outputs and Analogue Channels On Off low tone Hi tone ...
Page 61: ...Site Information ...
Page 63: ...Labelling ...
Page 67: ...Zones ...
Page 74: ...Condition Code Analysis Subfault Exception BS panel V3 EN54 panel V4 ...
Page 76: ......
Page 93: ... Other Panel Functions ...
Page 105: ...VigInSite ...
Page 112: ...Loop Diagnostic Tool LDT ...
Page 119: ...LDT Earth Fault Earth fault Detected Click to Locate Earth fault The Loop will now reallocate ...
Page 120: ...LDT Earth Fault ...
Page 122: ...LDT Reports cont Extracts from an Engineer report ...
Page 123: ...EN54 Part 23 Overview ...
Page 126: ...Wall Mounted VADs CEILING MOUNTED C 6 16 16m ...