ES-50X Series Manual —
P/N LS10129-000FL-E:D 4/26/2021
73
Master Programming Level
Programming
Control Module Auto Silence
(Canadian Mode Only)
The Control Module Auto Silence feature is only available when the FACP is in Canadian mode of operation.
When enabled, this feature automatically silences all silenceable control modules after a programmed length of
time. To enable this feature and program the time delay before Control Module Auto Silence activation, press
2
while viewing Timer Screen #2. The following screens will be displayed:
To disable the Auto Silence feature, press
1
for
No
while viewing Control Module Auto Silence Screen #1. To enable the Auto Silence fea-
ture, press the number corresponding to the time delay which will elapse before Control Module Auto Silence activates. This information
will be stored in memory and the display will return to Timer Screen #2.
In Suite Silence
(Canadian Mode Only)
The In Suite Silence feature is only available when the FACP is in Canadian mode of operation. When enabled,
this feature automatically silences all active outputs mapped to the In Suite Silence Zone (as described in “Spe-
cial Purpose Zone” on page 66) after a programmed length of time. Pressing
1
while viewing Timer Screen #3
will display the following.
A flashing cursor will appear in the lower left corner of the display. Type the two digit in suite silence delay in minutes (01 to 30 minute
delay). The default time is 30 minutes. When the second digit is entered, the display will return to the Delay Screen which will indicate the
new delay time.
Suite Resound
(Canadian Mode Only)
The Suite Resound feature is only available when the FACP is in Canadian mode of operation. When enabled,
this feature will resound all outputs and NACs that were silenced by the In Suite Silence timer (if there is an
unacknowledged fire alarm on the panel) after a programmed length of time. Once the Suite Resound Timer
occurs, additional fire alarms on the system will not restart the In Suite Silence timer. Pressing
2
while viewing
Timer screen #3 will display the following.
A flashing cursor will appear in the lower left corner of the display. Type the twp digit in suite silence delay in minutes (01 to 10 minute
delay). The default time is 1 minute. When the second digit is entered, the display will return to the Delay Screen which will indicate the new
delay time. The Suite Resound Timer starts when the In Suite Silence timer expires.
NACS (Notification Appliance Circuits)
The options for the NACs on the control panel main circuit board can be configured by pressing
2
while view-
ing System Setup Screen #2. The following screens will be displayed:
The Notification Appliance Circuits can be configured independently by pressing
1
for NAC 1 or
2
for NAC 2.
TIMER
1=AC LOSS DELAY
2=CTRL MOD DLY
3=CTRL AUTO SIL. 000
Timer Screen #2
CTRL AUTO SILENCE
1=NO
2=5 MINUTES
3=10 MINUTES
Control Auto Silence Screen #1
CTRL AUTO SILENCE
1=30 MINUTES
Control Auto Silence Screen #2
CTRL AUTO SILENCE
1=15 MINUTES
2=20 MINUTES
3=25 MINUTES
Control Auto Silence Screen #3
TIMER
1=IN SUITE SIL. 30
2=SUITE RESOUND 01
Timer Screen #3
IN SUITE SILENCE
RANGE 1-30 MINUTES
44
In Suite Silence Delay Screen
NOTE:
If the In Suite Silence Timer is set shorter than the Silence Inhibit feature, the system will not silence.
TIMER
1=IN SUITE SIL. 30
2=SUITE RESOUND 01
Timer Screen #3
SUITE RESOUND
RANGE 1-10 MINUTES
44
In Suite Resound Screen
SYSTEM SETUP
1=TIMERS
2=NACS
3=RELAYS
System Setup Screen #2
NACS
1=NAC 1
2=NAC 2
NAC Selection Screen