Programming
Maintenance Programming Level
3.6.6 Zone Setup
Pressing
3
while viewing Maintenance Screen #2 will display the following screen:
Pressing
1
while viewing Zone Setup screen will display the following screen:
A flashing cursor appears to the right of the Z. To enable a zone, enter the three digit zone number (000 - 049). After the second digit is
entered, the zone will be enabled and the cursor will return to the original position. The next zone to be enabled can then be entered. Press
Esc (Escape) to return to the previous screen.
Pressing
2
while viewing Zone Setup screen will display the following screen:
A flashing cursor appears to the right of the Z. To disable a zone, enter the three digit zone number (000 - 049). After the second digit is
entered, the zone will be disabled and the cursor will return to the original position. The next zone to be disabled can then be entered. Press
Esc
(Escape) to return to the previous screen.
Pressing
3
while viewing Zone Setup screen will display the following screens:
Zones 047, 048, 049, and 046 can be programmed for normal zone operation or for special purpose applications. In the above illustration, the
four zones are shown Off, which means they can be programmed to function in the same manner as all other zones, by assigning them to
input and output devices in the Programming Zone Assignment Screen.
Pressing
1
will cause the display to change to
PAS 47 On
. Each press of the
1
key will cause the display to toggle between
PAS 47 On
and
PAS 47 Off
. When Zone 047 is programmed On, a PAS (Positive Alarm Sequence) activation of any smoke detector will cause Zone 047 to
activate. By assigning Zone 047 to a control module in the Programming Zone Assignment Screen, an output device connected to the control
module can be used to indicate a PAS condition in the control panel.
Do not assign Zone 047 to a Notification Appliance Circuit when using
this zone to indicate a PAS condition.
Pressing
2
will cause the display to change to
Pre-signal 48 On
. Each press of the
2
key will cause the display to toggle between
Pre-signal
48 On
and
Pre-signal 48 Off
. When Zone 048 is programmed On, a Pre-signal activation of any device will cause Zone 018 to activate. By
assigning Zone 048 to a control module in the Programming Zone Assignment Screen, an output device connected to the control module can
be used to indicate a Pre-signal condition in the control panel.
Do not assign Zone 048 to a Notification Appliance Circuit when using this
zone to indicate a Pre-signal condition.
Pressing
3
will cause the display to change to
Two Stage 49 On
. Each press of the
3
key will cause the display to toggle between
Two Stage
49 On
and
Two Stage 49 Off.
” on page 75 for a description of this feature. Two-stage operation cannot be
used at the same time as the in-suite silence feature.
Pressing
1
while viewing the Special Purpose Zone Screen #2 will cause the display to change to
Local Alm 46 On
. Each press of the
1
key
will cause the display to toggle between
Local Alm 46 On
and
Local Alm 46 Off
. When Zone 046 is programmed On, a Local Alarm activa-
tion of any smoke detector will cause Zone 046 to activate. By assigning Zone 046 to a control module in the Programming Zone Assign-
ment Screen, an output device connected to the control module can be used to indicate a local alarm condition in the control panel.
Local
Alarm Zone alarms are not reported to the Central Station.
PROGRAMMING
1=WALKTEST
2=SYSTEM
3=ZONE SETUP
Maintenance Screen #2
ZONE SETUP
1=ENABLE
2=DISABLE
3=SPECIAL PURPOSE
Zone Setup Screen
ZONE TO ENABLE
Z
444
Enable Screen
ZONE TO DISABLE
Z
444
Disable Screen
SPEC PURPOSE ZONE
1=PAS 47 OFF
2=PRE-SIGNAL 48 OFF
3=TWO STAGE 49 OFF
Special Purpose Screen #1
SPEC PURPOSE ZONE
1=LOCAL ALM 46 OFF
Special Purpose Screen #1