Operating Instructions
Read Status
Entering the three digit detector address will cause the control panel to display the current status of the selected device. For example, if a
detector with address
001
on the SLC loop is entered, a display similar to the following will appear:
The information in the preceding display includes:
•
NORMAL
- the present status (could also be ALARM, TROUBL, DISABL, etc.)
•
SMOKE (PHOTO)
- the device type which is a photoelectric smoke detector (could also be ION for ionization smoke detector)
•
NORTH CLASSROOM
- the Adjective/Noun label for this device
•
Z005
- the first of five possible assigned software zones
•
1D001
-
1
= SLC Loop,
D
= Detector,
001
= Address 001
•
V - Alarm Verification Enabled (V = Yes, * = No)
•
S - Silenceable for control modules (S = Yes, * = No)
•
W - Walktestable for control and monitor modules (W = Yes, * = No)
Pressing the down arrow key, while viewing the screen shown above, will allow the operator to view additional programming informa-
tion about the selected device, such as:
•
Enable/Disable Status
•
Device Type
•
Alarm Verification On/Off (for detectors)
•
Walktest Yes/No
•
PAS (Positive Alarm Sequence) Yes/No (for detectors only)
•
Pre-Signal Yes/No (for detectors and monitor modules)
•
Zone Assignments (five maximum)
•
Chamber Value
•
Adjective/Noun descriptor
•
Silenceable Yes/No (for control modules)
•
Wireless Yes/No (for detectors only)
•
Sounder Base Yes/No (for detectors only)
•
Sounder Base Values and Zone Assignments (for detectors only)
4.23.2 Zones
Pressing
2
while viewing Read Status Screen #1 will cause the following screens to be displayed:
From the preceding screens, the control panel operator can view:
•
Zones Installed
- all software zones programmed into the system (49 maximum)
•
Zones Enabled
- all software zones that are enabled
•
Zones Disabled
- all software zones that have been disabled
•
Special Purpose
- on or off programming for Special Purpose Zones 047 reserved for PAS, 048 reserved for Pre-signal, 049
reserved for Two Stage, and 046 for Local Alarm
•
Zone Type
- the Type assigned to each installed zone (default is Alarm)
4.23.3 Trouble Reminder
Pressing
1
while viewing Read Status Screen #2 will display the following screen:
The screen indicates whether the Trouble Reminder feature is set to sound every 4 or 24 hours.
NORMAL SMOKE(PHOTO)
NORTH CLASSROOM
Z005
V 1D001
READ STATUS
1=SYSTEM POINT
2=ZONES
Read Status Screen #1
ZONES
1=ZONES INSTALLED
2=ZONES ENABLED
3=ZONES DISABLED
Zones Screen #1
ZONES
1=SPECIAL PURPOSE
2=ZONE TYPE
Zones Screen #2
READ STATUS
1=TROUBLE REMINDER
2=TIMERS
3=NAC
Read Status Screen #2
TROUBLE REMINDER
TROUBLE REM 24HR