60
ES-50X Series Manual —
P/N LS10129-000FL-E:D 4/26/2021
Programming
Master Programming Level
Monitor module type selection will affect the function of the point as follows:
Monitor Type
Action When Activated
Pull-Station
Fire Alarm
User-Defined-1
same as previous (Pull-Station)
Waterflow
Fire Alarm Delayed
User-Defined-2
same as previous (Waterflow)
Monitor
Fire Alarm
User-Defined-3
same as previous (Monitor)
Future
not used
Future
not used
Smoke-Conventional
Fire Alarm
User-Defined-5
same as previous (Smoke-Conventional)
Heat Conventional
Fire Alarm
User-Defined-6
same as previous (Heat-Detector)
Medic Alert
1
1 Combination systems employing these non-fire monitor types require the SLC loop to be programmed
by the installer for Class B operation and isolator modules must be employed on each non-fire branch
of the SLC as shown in the SLC Wiring Manual (document number 51309). Fire and non-fire devices
must not be used on the same SLC branch. For UL2017 compliance, The ANN-LED annunciator must
be used to indicate the active, dedicated zone or device
General Purpose Signaling, latching
User-Defined-7
same as previous (Medic-Alert)
Hazard Alert
General Purpose Signaling, latching
User-Defined-8
same as previous (Hazard-Alert)
Tornado Alert
General Purpose Signaling, latching
User-Defined-9
same as previous (Tornado-Alert)
Phone
Active Phone (LCD display only)
User-Defined-10
same as previous (Phone)
Tamper
Supervisory, nonlatching (tracking)
User-Defined-11
same as previous (Tamper)
Supervisory
Supervisory, latching
User-Defined-12
same as previous (Supervisory)
Supervisory AR
2
2 For entries ending in AR, AR refers to AutoResettable.
Supervisory, nonlatching (tracking)
User-Defined-13
same as previous (Supervisory-AR)
HVAC OVRRIDE
3
3 For HVAC RESTART and HVAC OVRRIDE descriptions, refer to “Monitor Module Operation” on
Switch Supervisory, nonlatching (tracking)
Power Monitor
Power Fault
User-Defined-14
same as previous (Power Monitor)
Trouble Monitor
Trouble
User-Defined-15
same as previous (Trouble Monitor)
Process Monitor
General Purpose Signaling, latching
User-Defined 16
same as previous (Process-Monitor)
Process Monitor AR
General Purpose Signaling, nonlatching (tracking)
User-Defined-17
same as previous (Process-Monitor-AR)
Future
not used
Future
not used
Ack Switch
Acts like panel Acknowledge Key
Sil Switch
Acts like panel Silence Key
Reset Switch
Acts like panel Reset Key
Drill Switch
Acts like panel Drill Key
PAS Bypass
PAS Disable
Switch (see note 2)
Drill Switch AR
Acts like panel Drill Key, non-latching (tracking)
Wireless Gateway
SWIFT gateway needs this type to display wireless troubles at the FACP
Table 3.1 Monitor Types