ES-50X Series Manual —
P/N LS10129-000FL-E:D 4/26/2021
51
Master Programming Level
Programming
Detector Programming
Pressing
1
, while viewing the Point Program Screen, will allow the programmer to add, delete or change the programming of an addressable
detector. The following screen will be displayed by the control panel:
Add Detector
Pressing
1
while viewing the Detector Screen will display the following screen which allows the programmer to add a new detector address
to programming:
A flashing cursor will appear in the position of the first asterisk to the left. The programmer keys in the three digit detector address, such as
005. The screen will then ask whether the detector being added is wireless.
Select
1
for wired detector or
2
for wireless detector. When the choice is selected, the following screen will be displayed:
Press the down arrow key to view additional choices. Press the number corresponding to the desired selection to program that type to the
newly added detector. If the selected detector is a multi-criteria Fire (Photo)/CO detector, select
1
for
Fire CO.
When the type has been
selected, the following screen will be displayed:
The programmer can continue adding detectors by pressing the ESC key which will return the display to the Add Detector Screen.
Delete Detector
Pressing
2
in the Detector Screen will display the Delete Detector Screen which allows the programmer to delete
a specific detector:
A flashing cursor will appear in the position of the first asterisk to the left. The programmer keys in the three digit detector address, such as
005. When the last digit is keyed-in, the following screen will be displayed:
The programmer can continue deleting detectors by pressing the
ESC
key which will return the display to the Delete Detector Screen.
DETECTOR
1=ADD
2=DELETE
3=EDIT
Detector Screen
ADD DETECTOR
ENTER DETECTOR#
444
Add Detector Screen
ADD DETECTOR
1=DETECTOR
2=DETECTOR:WIRELESS
Add Detector Screen
DETECTOR TYPE
1=SMOKE(PHOTO)
2=USER-DEFINED-1
3=SMOKE(ION)
DETECTOR TYPE
1=FIRE CO
2=USER-DEFINED-12
through
ADD DETECTOR
DETECTOR# 005
IS ADDED
NOTE:
The system
must
be monitored by a Supervising Station when using carbon monoxide detection per The Requirements for the
Installation of Carbon Monoxide (CO) Detection and Warning Equipment, NFPA 720.
DETECTOR
1=ADD
2=DELETE
3=EDIT
Detector Screen
DELETE DETECTOR
ENTER DETECTOR#
444
Delete Detector Screen
DELETE DETECTOR
DETECTOR# 005
IS DELETED