Honeywell FF-SRS5988 Instructions For Use Manual Download Page 7

107018-04 EN FR26 GLO 1198 Printed in Germany

 

7

APPLICATION EXAMPLES

FIG 10.  DUAL CHANNEL EMERGENCY STOP CIRCUITRY (WITH CROSS-FAULT MONITORING)

Start

L1

Honeywell

FF-SRS 5988

Emergency

stop

N

Y1 Y2

X1 X2

S33

S11

A3
(+)

S34

(A)

(B)

A4

(-)

(C)

Machine

Control

Power

Fuse

Fuses

This circuit has redundancy in the emergency-stop control circuit and therefore offers the highest
possible safety level.

FUNCTIONAL DESCRIPTION:

After activation of the Emergency-stop push button, the K1 and K2 LED’s will turn OFF, indicating that the
two internal safety relays K1 and K2 are de-energized. The normally open safety outputs 13/14... 63/64 will
open.
There exist two different start modes:
Manual start mode
1. After  removing the stop condition, press and release the START push button to restart the safety control

module.

2. The K2 and K3 LED’s will turn ON indicating that the safety relays K2 and K3 are energized. The six

normally open safety contacts will close and the normally closed monitoring contact will open allowing the
machine to operate.

Automatic start mode
1.  After removing the stop condition, the safety control module will reset within 1 sec.
The K2 and K3 LED’s will turn ON indicating that the safety relays K2 and K3 are energized. The six
normally open safety contacts will close and the normally closed monitoring contact will open allowing the
machine to operate.

APPLICATION NOTES:

NOTE (A): 

Dual channel safety devices:

This may be an emergency stop push button in series with dual output safety switching devices (OSSD)
such as
- safety light curtains (FF-SB, FF-LS),
- safety mat (FF-SM),
- single beam (FF-SPS), modular safety light curtains (FF-SC),
- safety laser scanner (FF-SE),
- dual output safety limit or interlock switches (for example, 2CLS and GK, see fig. 12).

NOTE (B):

 Y1 and Y2 are jumpered if no external contactors have to be monitored

NOTE (C):

 Start mode:

Manual start mode: Insert start push-button between S33/S34; no jumper must be set between X1/X2
Automatic start mode: Insert jumper between X1/X2

IMPROPER AUTOMATIC START MODE IN PERIMETER GUARDING APPLICATIONS

 If the module is in the automatic start mode, another part of the safety control circuitry must keep the

latched function engaged.

Failure to comply with these instructions could result in death or serious injury.

Summary of Contents for FF-SRS5988

Page 1: ... or manual start mode cross fault monitoring and external relays monitoring APPROVALS CE The product packaging and documentation of FF SR Series products carry the CE mark following the examination by BG German Berufsgenossenschaft E MIII The CE declaration of conformity is available upon request cULus pending This product is pending approval by Underwriters Laboratories Inc according to Canadian ...

Page 2: ... 00 Operating frequency 600 switching cycles hour Output contact fuse rating Time delay 6 A max Mechanical life Thirty million switching operations General Temperature range 15 C to 55 C 5 F to 131 F at 90 humidity max Sealing Housing IP 40 Terminals IP 20 Housing material Thermoplastic Vibration resistance Amplitude 0 35 mm Frequency 10 to 55 Hz Wire connector connection 1 x 4 mm 2 solid max 12 A...

Page 3: ...Y Control Reliability means that the device system or interface shall be designed constructed and installed such that a single component failure within the device interface or system shall not prevent normal stopping action from taking place but shall prevent a successive machine cycle ANSI B11 19 1990 5 5 OSHA 29 CFR 1910 217 states that the control system shall be constructed so that a failure w...

Page 4: ...AM PE S23 64 S21 K2 K23 K2 K1 K3 Power K2 K3 24V 14 24 34 44 54 82 K3 K2 K23 Overvoltage and short circuit protection Monitoring logic 23 A1 A2 A4 S11 A3 Y1 Y2 S 33 S 34 S 12 S 12 S 22 13 33 43 53 63 81 FUNCTIONAL DESCRIPTION In the manual start mode the module accepts input from the safety device light curtain safety mat safety switches etc between S11 S12 and S21 S23 after activation of the star...

Page 5: ...The Power LED indicates power is applied to the safety control module Illuminated K2 and or K3 LED s indicate s that the corresponding internal safety relay is energized Both K2 and K3 relays must be energized to have the normally open contacts 13 14 63 64 in a closed position If one of the safety relays de energizes the normally closed contact will close FIG 8 MODULE FRONT PANEL K2 K 23 K3 13 A1 ...

Page 6: ...eries or 81 82 inside the Final Switching Device FSD monitoring loop circuit Y1 Y2 This connection will ensure correct operation of the external relays or the Extension module after each FF SRS5988 activation If the FF SRS5988 is not activated often the customer is responsible for accomplishing any additional test procedures of the external safety components For instance this testing can be done b...

Page 7: ...omatic start mode 1 After removing the stop condition the safety control module will reset within 1 sec The K2 and K3 LED s will turn ON indicating that the safety relays K2 and K3 are energized The six normally open safety contacts will close and the normally closed monitoring contact will open allowing the machine to operate APPLICATION NOTES NOTE A Dual channel safety devices This may be an eme...

Page 8: ...cating that the safety relays K2 and K3 are energized The six normally open safety contacts will close and the normally closed monitoring contacts will open allowing the machine to operate APPLICATION NOTES Note A SINGLE CHANNEL SAFETY DEVICES This may be a single output safety device such as a safety limit or interlock switch for example CLS GK and GSS Note B EXTERNAL CONTACTORS If contact reinfo...

Page 9: ...lly open safety outputs 13 14 63 64 will open relaying the stop condition to the machine control circuitry After closing the door S1 and S2 close and the internal relays K2 and K3 will energize The six normally open safety contacts will close and an external manual restart sequence may then be initiated allowing the machine to operate IMPORTANT NOTICES SAFETY LIMIT SWITCH SEQUENCE In order to let ...

Page 10: ...Printed in Germany FIG 13 FF SRS5988 TROUBLESHOOTING FLOW DIAGRAM PAGE 1 OF 3 Machine Down Yes No Apply correct voltage Replace the safety module Yes Is the Power LED ON Is the power applied within specifications No Go to Figure 14 ...

Page 11: ...le Ensure the FSD monitoring loop Y1 Y2 is closed when the external start push button is activated and opened when the pushbutton is released this tests the correct operation of the push button or optional external relays contactors Is the problem resolved Are the K2 and K3 LEDs ON Are the outputs contacts 13 14 63 64 closed and is 81 82 opened From Fig 15 Yes No No Go to Fig 15 From Fig 13 Ensure...

Page 12: ...ween S12 A4 Disconnect S21 Is input channel two closed Also is there less than 68 Ohms between S21 S23 and more than 21 Vdc between S22 A3 Disconnect S11 and ensure input channel one is closed less than 68 Ohms between S11 S12 and more than 21 Vdc between S12 A4 No No Yes to all questions Yes Reconnect S11 Correct replace the external sensor s wiring supply voltage etc From Fig 14 Go to Page 2 Ens...

Page 13: ...While we provide application assistance personally and through our literature and the Honeywell Website it is up to the customer to determine the suitability of the product in the application Specifications may change at any time without notice The information we supply is believed to be accurate and reliable as of this printing However we assume no responsibility for its use SALES AND SERVICE For...

Reviews: