107018-04 EN FR26 GLO 1198 Printed in Germany

SPECIFICATIONS

Input

Nominal voltage

(Dual voltage device)

120 Vac (-20%, +10%) / 24Vdc (-10%, +20%)
230 Vac (-20%, +10%) / 24Vdc (-10%, +20%)

Nominal power consumption

DC: 3 W; AC: 6 VA

Nominal frequency

50 to 60 Hz

Start time

Manual START function: 30ms
Automatic START function: 1 s

Nominal voltage at S11

 at S21

24 Vdc (provided by control module)
0 V

Input current between

S11/S12 and S21/S23

110 mAdc

Minimum voltage at S12/A4

and at S22/A4

21 Vdc when activated

Cable resistance between

S11/S12 and S21/S23

68 

 (max.)

Output

Contact complement

6 NO, 1 NC contacts

Response time

Opening of inputs (S11/S12; S21/S23):
30 ms;
Opening in supply circuit: 50 ms

Contact type

Safety relay, positive-guided

Switching Capability

Current Range (min. to max.)

Voltage Range (min. to

max.)

Switching Capability per

AC15

(EN 60 947-5-1)

Power factor = 1 with resistive load
1 mA to 10A (see Caution)
0.1 to 250 Vac/dc
NO contact: 5 A/ 230 V
NC contact: 2A / 230 V

Typical Electrical Life

Expectancy 3A

5A

10A

Power factor = 1 at 230 Vac/dc (see fig. 1,
note 1)
1,000,000 operations
500,000 operations
220,000 operations

Typical Power Factor (cos 

ϕ

)

0.3
0.5
0.7
1.0

Limitation Factor (see fig. 2, note 2)
0.45
0.70
0.85
1.00

Operating frequency

600 switching cycles/hour

Output contact fuse rating

Time delay 6 A (max.)

Mechanical life

Thirty million switching operations

General

Temperature range

-15

°

C to + 55

°

C (5

°

F to 131

°

F) at 90%

humidity (max.)

Sealing

Housing IP 40; Terminals IP 20

Housing material

Thermoplastic

Vibration resistance

Amplitude 0.35 mm; Frequency 10 to 55 Hz

Wire/connector connection

1 x 4 mm

2

 solid (max.) [12 AWG] or 2 x 1.5

mm

2

 (max.) [16 AWG] stranded wire with

sleeve DIN 46288

Wire/connector attachment

Removable  terminals  block  with M3.5
screws; wire contacts are enclosed to prevent
electrical shock

Mounting

Quick install rail mounting EN 50022-35;
width: 35 mm  (1.38 in.)

Weight

840 g (1.85 lb.)

NOTE 1: 

Install arc suppression device across load to avoid module contact

arcing and ensure specified relay life expectancy.

NOTE 2  Total operations = operations at power factor 1 multiplied by the
limitation factor.  If the power factor is 0.5 at 230 Vac, 3A (1,000,000
operations), the limitation factor is 0.70.  1,000,000 x 0.70 = 700,000 total
operations.

FIG 1.  CONTACT LIFE FOR
100% RESISTIVE LOAD (typical)
(note 1)
power factor = 1 (cos 

ϕ

)

FIG 2.  LIMITATION FACTOR
FOR INDUCTIVE LOADS (note 2)
power factor < 1 (cos 

ϕ

)

CONTACT DAMAGE
To ensure the 1 mA capability
during the lifetime of the contact,
NEVER exceed 300 mA and 60V.

Failure to comply with these
instructions will result in loss of
low current switching capability.

Summary of Contents for FF-SRS5988

Page 1: ... or manual start mode cross fault monitoring and external relays monitoring APPROVALS CE The product packaging and documentation of FF SR Series products carry the CE mark following the examination by BG German Berufsgenossenschaft E MIII The CE declaration of conformity is available upon request cULus pending This product is pending approval by Underwriters Laboratories Inc according to Canadian ...

Page 2: ... 00 Operating frequency 600 switching cycles hour Output contact fuse rating Time delay 6 A max Mechanical life Thirty million switching operations General Temperature range 15 C to 55 C 5 F to 131 F at 90 humidity max Sealing Housing IP 40 Terminals IP 20 Housing material Thermoplastic Vibration resistance Amplitude 0 35 mm Frequency 10 to 55 Hz Wire connector connection 1 x 4 mm 2 solid max 12 A...

Page 3: ...Y Control Reliability means that the device system or interface shall be designed constructed and installed such that a single component failure within the device interface or system shall not prevent normal stopping action from taking place but shall prevent a successive machine cycle ANSI B11 19 1990 5 5 OSHA 29 CFR 1910 217 states that the control system shall be constructed so that a failure w...

Page 4: ...AM PE S23 64 S21 K2 K23 K2 K1 K3 Power K2 K3 24V 14 24 34 44 54 82 K3 K2 K23 Overvoltage and short circuit protection Monitoring logic 23 A1 A2 A4 S11 A3 Y1 Y2 S 33 S 34 S 12 S 12 S 22 13 33 43 53 63 81 FUNCTIONAL DESCRIPTION In the manual start mode the module accepts input from the safety device light curtain safety mat safety switches etc between S11 S12 and S21 S23 after activation of the star...

Page 5: ...The Power LED indicates power is applied to the safety control module Illuminated K2 and or K3 LED s indicate s that the corresponding internal safety relay is energized Both K2 and K3 relays must be energized to have the normally open contacts 13 14 63 64 in a closed position If one of the safety relays de energizes the normally closed contact will close FIG 8 MODULE FRONT PANEL K2 K 23 K3 13 A1 ...

Page 6: ...eries or 81 82 inside the Final Switching Device FSD monitoring loop circuit Y1 Y2 This connection will ensure correct operation of the external relays or the Extension module after each FF SRS5988 activation If the FF SRS5988 is not activated often the customer is responsible for accomplishing any additional test procedures of the external safety components For instance this testing can be done b...

Page 7: ...omatic start mode 1 After removing the stop condition the safety control module will reset within 1 sec The K2 and K3 LED s will turn ON indicating that the safety relays K2 and K3 are energized The six normally open safety contacts will close and the normally closed monitoring contact will open allowing the machine to operate APPLICATION NOTES NOTE A Dual channel safety devices This may be an eme...

Page 8: ...cating that the safety relays K2 and K3 are energized The six normally open safety contacts will close and the normally closed monitoring contacts will open allowing the machine to operate APPLICATION NOTES Note A SINGLE CHANNEL SAFETY DEVICES This may be a single output safety device such as a safety limit or interlock switch for example CLS GK and GSS Note B EXTERNAL CONTACTORS If contact reinfo...

Page 9: ...lly open safety outputs 13 14 63 64 will open relaying the stop condition to the machine control circuitry After closing the door S1 and S2 close and the internal relays K2 and K3 will energize The six normally open safety contacts will close and an external manual restart sequence may then be initiated allowing the machine to operate IMPORTANT NOTICES SAFETY LIMIT SWITCH SEQUENCE In order to let ...

Page 10: ...Printed in Germany FIG 13 FF SRS5988 TROUBLESHOOTING FLOW DIAGRAM PAGE 1 OF 3 Machine Down Yes No Apply correct voltage Replace the safety module Yes Is the Power LED ON Is the power applied within specifications No Go to Figure 14 ...

Page 11: ...le Ensure the FSD monitoring loop Y1 Y2 is closed when the external start push button is activated and opened when the pushbutton is released this tests the correct operation of the push button or optional external relays contactors Is the problem resolved Are the K2 and K3 LEDs ON Are the outputs contacts 13 14 63 64 closed and is 81 82 opened From Fig 15 Yes No No Go to Fig 15 From Fig 13 Ensure...

Page 12: ...ween S12 A4 Disconnect S21 Is input channel two closed Also is there less than 68 Ohms between S21 S23 and more than 21 Vdc between S22 A3 Disconnect S11 and ensure input channel one is closed less than 68 Ohms between S11 S12 and more than 21 Vdc between S12 A4 No No Yes to all questions Yes Reconnect S11 Correct replace the external sensor s wiring supply voltage etc From Fig 14 Go to Page 2 Ens...

Page 13: ...While we provide application assistance personally and through our literature and the Honeywell Website it is up to the customer to determine the suitability of the product in the application Specifications may change at any time without notice The information we supply is believed to be accurate and reliable as of this printing However we assume no responsibility for its use SALES AND SERVICE For...