SPECIFICATIONS
Input
Nominal voltage
(Dual voltage device)
120 Vac (-20%, +10%) / 24Vdc (-10%, +20%)
230 Vac (-20%, +10%) / 24Vdc (-10%, +20%)
Nominal power consumption
DC: 3 W; AC: 6 VA
Nominal frequency
50 to 60 Hz
Start time
Manual START function: 30ms
Automatic START function: 1 s
Nominal voltage at S11
at S21
24 Vdc (provided by control module)
0 V
Input current between
S11/S12 and S21/S23
110 mAdc
Minimum voltage at S12/A4
and at S22/A4
21 Vdc when activated
Cable resistance between
S11/S12 and S21/S23
68
Ω
(max.)
Output
Contact complement
6 NO, 1 NC contacts
Response time
Opening of inputs (S11/S12; S21/S23):
30 ms;
Opening in supply circuit: 50 ms
Contact type
Safety relay, positive-guided
Switching Capability
Current Range (min. to max.)
Voltage Range (min. to
max.)
Switching Capability per
AC15
(EN 60 947-5-1)
Power factor = 1 with resistive load
1 mA to 10A (see Caution)
0.1 to 250 Vac/dc
NO contact: 5 A/ 230 V
NC contact: 2A / 230 V
Typical Electrical Life
Expectancy 3A
5A
10A
Power factor = 1 at 230 Vac/dc (see fig. 1,
note 1)
1,000,000 operations
500,000 operations
220,000 operations
Typical Power Factor (cos
ϕ
)
0.3
0.5
0.7
1.0
Limitation Factor (see fig. 2, note 2)
0.45
0.70
0.85
1.00
Operating frequency
600 switching cycles/hour
Output contact fuse rating
Time delay 6 A (max.)
Mechanical life
Thirty million switching operations
General
Temperature range
-15
°
C to + 55
°
C (5
°
F to 131
°
F) at 90%
humidity (max.)
Sealing
Housing IP 40; Terminals IP 20
Housing material
Thermoplastic
Vibration resistance
Amplitude 0.35 mm; Frequency 10 to 55 Hz
Wire/connector connection
1 x 4 mm
2
solid (max.) [12 AWG] or 2 x 1.5
mm
2
(max.) [16 AWG] stranded wire with
sleeve DIN 46288
Wire/connector attachment
Removable terminals block with M3.5
screws; wire contacts are enclosed to prevent
electrical shock
Mounting
Quick install rail mounting EN 50022-35;
width: 35 mm (1.38 in.)
Weight
840 g (1.85 lb.)
NOTE 1:
Install arc suppression device across load to avoid module contact
arcing and ensure specified relay life expectancy.
NOTE 2 Total operations = operations at power factor 1 multiplied by the
limitation factor. If the power factor is 0.5 at 230 Vac, 3A (1,000,000
operations), the limitation factor is 0.70. 1,000,000 x 0.70 = 700,000 total
operations.
FIG 1. CONTACT LIFE FOR
100% RESISTIVE LOAD (typical)
(note 1)
power factor = 1 (cos
ϕ
)
FIG 2. LIMITATION FACTOR
FOR INDUCTIVE LOADS (note 2)
power factor < 1 (cos
ϕ
)
CONTACT DAMAGE
To ensure the 1 mA capability
during the lifetime of the contact,
NEVER exceed 300 mA and 60V.
Failure to comply with these
instructions will result in loss of
low current switching capability.