 APPLICATION WARNINGS

 

 IMPROPER INPUT CONNECTIONS

  To ensure the highest level of safety, connect two safety device outputs into the two input channels of the

FF-SRS5988 safety module. Then, a cross fault between the two channels will shut down the module.

  If the safety device provides one safety output only (e.g., a switch driven by a direct acting mechanism like

some GK, GSS, CLS or Emergency Stop push buttons), connect the FF-SRS5988 module as shown in the
single input channel example To avoid any short circuit possibilities on this single input channel, use
conduit to protect wiring and additional protection for the terminal strips inside the machine cabinets.

 The cable resistance between S11/S12 or S21/S23 should not exceed 68

 and the voltage between

S12/A4 and S22/A4 should not be lower than 21Vdc.

 IMPROPER EMERGENCY STOP CONNECTION

 To ensure maximum safety, connect two normally closed contacts of the Emergency Stop into the input

channel of the FF-SRS5988 module.

 IMPROPER AUTOMATIC START MODE IN PERIMETER GUARDING APPLICATIONS

 If the module is in the automatic start mode, another part of the safety control circuitry must keep the

latched function engaged.

 IMPROPER PUSH BUTTON USE (MANUAL START MODE)

 To ensure maximum safety when using an external start push button, always design the circuitry for

manual start mode (see Mode Setting, page 4).

  Ensure the location of the manual start function is outside of the danger zone and provides the operator

with a clear view of the zone.

  For perimeter guarding solutions, the operator should not be able to reach manual start from the danger

zone.

  A Programmable Logic Controller (PLC) must NOT be able to override a manual start function.

 CONTACT WELDING

  Always protect all safety contacts with correctly rated fuses.  These fuses must never exceed the rated FF-

SRS5988 safety output capability to prevent contact welding.

 IMPROPER EXTERNAL SAFETY RELAY MONITORING

 When using additional safety relays (or the FF-SRE Extension module), always connect one normally

closed contact of each relay in series (or 81/82) inside the Final Switching Device (FSD) monitoring loop
circuit (Y1/Y2).  This connection will ensure correct operation of the external relays or the Extension
module after each FF-SRS5988 activation.

  If the FF-SRS5988 is not activated often, the customer is responsible for accomplishing any additional test

procedures of the external safety components.  For instance, this testing can be done by removing the
power from the FF-SRS5988 at machine power up every day.

 IMPROPER ARC SUPPRESSOR INSTALLATION

  NEVER install an arc suppressor across the safety output contact of the safety control module.

  ALWAYS install arc suppressors across the coils of external safety relays.

 IMPROPER DOOR MONITORING

  If two safety switches are used to monitor a door’s closed position, connect one safety contact of the first

switch between input S11/S12 and one safety contact of the second switch between S21/S23 of the FF-
SRS 5988 Emergency stop module.

 IMPROPER SYSTEM SAFETY LEVEL

  Several safety components can be connected to a FF-SRS5988 control module.  If more than one safety

output is connected to one of the two input channels of the control module, always connect these safety
outputs in series.  Parallel wiring of multiple outputs into a single channel can defeat the channel and cause
an unsafe condition.

  Individually activate and check all of the safety devices connected to a FF-SRS5988 control module to

ensure proper operation.

 IMPROPER EMERGENCY STOP PUSH BUTTON

  The Emergency Stop push button must be designed according to European (EN 418) and US safety

standards (NFPA 19). Under any condition, the Emergency Stop switch must be able to open its contacts
when activated.

 LONGER RESPONSE TIME

  The FF-SRS5988 module will have a longer response time (when the emergency push button is activated)

if the emergency stop push button is connected in series with the power supply of the module.  However,
connecting the emergency stop push button to the safety input channels will result in a shorter response
time.

IMPROPER USE OF THE NORMALLY CLOSED OUTPUT CONTACT

  Use the normally closed output contact (81/82) for monitoring purpose only.

  Do not use this 81/82 contact in the safety control circuitry of the machine.

Failure to comply with these instructions could result in death or serious injury.

Summary of Contents for FF-SRS5988

Page 1: ... or manual start mode cross fault monitoring and external relays monitoring APPROVALS CE The product packaging and documentation of FF SR Series products carry the CE mark following the examination by BG German Berufsgenossenschaft E MIII The CE declaration of conformity is available upon request cULus pending This product is pending approval by Underwriters Laboratories Inc according to Canadian ...

Page 2: ... 00 Operating frequency 600 switching cycles hour Output contact fuse rating Time delay 6 A max Mechanical life Thirty million switching operations General Temperature range 15 C to 55 C 5 F to 131 F at 90 humidity max Sealing Housing IP 40 Terminals IP 20 Housing material Thermoplastic Vibration resistance Amplitude 0 35 mm Frequency 10 to 55 Hz Wire connector connection 1 x 4 mm 2 solid max 12 A...

Page 3: ...Y Control Reliability means that the device system or interface shall be designed constructed and installed such that a single component failure within the device interface or system shall not prevent normal stopping action from taking place but shall prevent a successive machine cycle ANSI B11 19 1990 5 5 OSHA 29 CFR 1910 217 states that the control system shall be constructed so that a failure w...

Page 4: ...AM PE S23 64 S21 K2 K23 K2 K1 K3 Power K2 K3 24V 14 24 34 44 54 82 K3 K2 K23 Overvoltage and short circuit protection Monitoring logic 23 A1 A2 A4 S11 A3 Y1 Y2 S 33 S 34 S 12 S 12 S 22 13 33 43 53 63 81 FUNCTIONAL DESCRIPTION In the manual start mode the module accepts input from the safety device light curtain safety mat safety switches etc between S11 S12 and S21 S23 after activation of the star...

Page 5: ...The Power LED indicates power is applied to the safety control module Illuminated K2 and or K3 LED s indicate s that the corresponding internal safety relay is energized Both K2 and K3 relays must be energized to have the normally open contacts 13 14 63 64 in a closed position If one of the safety relays de energizes the normally closed contact will close FIG 8 MODULE FRONT PANEL K2 K 23 K3 13 A1 ...

Page 6: ...eries or 81 82 inside the Final Switching Device FSD monitoring loop circuit Y1 Y2 This connection will ensure correct operation of the external relays or the Extension module after each FF SRS5988 activation If the FF SRS5988 is not activated often the customer is responsible for accomplishing any additional test procedures of the external safety components For instance this testing can be done b...

Page 7: ...omatic start mode 1 After removing the stop condition the safety control module will reset within 1 sec The K2 and K3 LED s will turn ON indicating that the safety relays K2 and K3 are energized The six normally open safety contacts will close and the normally closed monitoring contact will open allowing the machine to operate APPLICATION NOTES NOTE A Dual channel safety devices This may be an eme...

Page 8: ...cating that the safety relays K2 and K3 are energized The six normally open safety contacts will close and the normally closed monitoring contacts will open allowing the machine to operate APPLICATION NOTES Note A SINGLE CHANNEL SAFETY DEVICES This may be a single output safety device such as a safety limit or interlock switch for example CLS GK and GSS Note B EXTERNAL CONTACTORS If contact reinfo...

Page 9: ...lly open safety outputs 13 14 63 64 will open relaying the stop condition to the machine control circuitry After closing the door S1 and S2 close and the internal relays K2 and K3 will energize The six normally open safety contacts will close and an external manual restart sequence may then be initiated allowing the machine to operate IMPORTANT NOTICES SAFETY LIMIT SWITCH SEQUENCE In order to let ...

Page 10: ...Printed in Germany FIG 13 FF SRS5988 TROUBLESHOOTING FLOW DIAGRAM PAGE 1 OF 3 Machine Down Yes No Apply correct voltage Replace the safety module Yes Is the Power LED ON Is the power applied within specifications No Go to Figure 14 ...

Page 11: ...le Ensure the FSD monitoring loop Y1 Y2 is closed when the external start push button is activated and opened when the pushbutton is released this tests the correct operation of the push button or optional external relays contactors Is the problem resolved Are the K2 and K3 LEDs ON Are the outputs contacts 13 14 63 64 closed and is 81 82 opened From Fig 15 Yes No No Go to Fig 15 From Fig 13 Ensure...

Page 12: ...ween S12 A4 Disconnect S21 Is input channel two closed Also is there less than 68 Ohms between S21 S23 and more than 21 Vdc between S22 A3 Disconnect S11 and ensure input channel one is closed less than 68 Ohms between S11 S12 and more than 21 Vdc between S12 A4 No No Yes to all questions Yes Reconnect S11 Correct replace the external sensor s wiring supply voltage etc From Fig 14 Go to Page 2 Ens...

Page 13: ...While we provide application assistance personally and through our literature and the Honeywell Website it is up to the customer to determine the suitability of the product in the application Specifications may change at any time without notice The information we supply is believed to be accurate and reliable as of this printing However we assume no responsibility for its use SALES AND SERVICE For...

Reviews: