41
RPS-1000 / RPS-1000B Manual - P/N 151153:N 08/09/2017
Notification Appliances
NOTE:
he maximum number of smoke detectors per zone is determined by both the current draw and the impedance of the smoke detector. If
too many smoke detectors are used on any zone, false alarms could occur.
NOTE:
Do not mix different models of detectors on any zone; false alarms could occur.
NOTE:
Control unit Smoke Reset Time must be programmed for a number greater than or equal to the maximum reset time of the smoke
detector.
Table A-1 Compatible Two-Wire Smoke Detectors Style B
Manufacturer
Model Name or Number
(Base model name or number in
parenthesis.)
Compatibility ID
# per Loop
Head
Base
Apollo
55000-350 (45681-200)
55000-
350
45681-200
15 / loop
55000-250 (45681-200)
55000-
250
45681-200
24 / loop
55000-225
55000-
225
45681-255, 256
45681-200, 220, 232,
251, 252
15 / loop for
Ion Detectors
15 / loop for
Photo Electric
Detectors
55000-226
55000-
226
55000-227
55000-
227
55000-325
55000-
325
55000-326
55000-
326
55000-327
55000-
327
55000-328
55000-
328
Hochiki
SLR-24
HD-3
HSC-220R(HB-72)
NS6-220 OR NS4-
220 (HB-3)
15 / loop
SLR-24H
SLR-24V
SLR-835
HD-3
14 / loop
SLR-835H
HD-5
System
Sensor
1400
A
N/A
16 / loop
1451 (B401B)
A
N/A
16 / loop
2100
A
N/A
20 / loop
2100T
A
N/A
20 / loop
2151 (B401)
A
N/A
16 / loop
2151T (B401)
A
N/A
16 / loop
2400
A
N/A
16 / loop
2400TH
A
N/A
16 / loop
2451 (B401B)
A
N/A
16 / loop
2451TH (B401B)
A
N/A
16 / loop
2W-B
A
N/A
20 / loop
2WT-B
A
N/A
20 / loop
2WTA-B
A
N/A
1 / loop
2WTR-B
A
N/A
1 / loop