21
RPS-1000 / RPS-1000B Manual - P/N 151153:N 08/09/2017
Hardware Installation
AC Power
Section 3: Hardware Installation
RPS-1000 installation involves the following steps:
•
AC power (Section 3.1) and backup battery connection (Section 3.2).
•
Physical connection from the FACP to the controlling RPS-1000 (see Section 3.3).
•
Setting an ID for the RPS-1000 (Section 3.3.1).
•
Physical connection of SBUS modules that will be powered by this RPS-1000 (Section 3.4).
•
Physical connection of any outputs (conventional relays, notification appliances, auxiliary power modules, and so on) that will be
powered by this RPS-1000. See Section 3.5.1 for notification appliance wiring information. Refer to the FACP Installation Manual
for software configuration information and other information about installing outputs.
3.1 AC Power
At installation, connect the AC terminals to 120 VAC source as shown in Figure 3.1. It may be necessary for a professional electrician to
make this connection.
The AC terminals are rated as 120 VAC, 50 or 60 Hz, 2.7 A (for the RPS-1000) or 240 VAC, 50 or 60 Hz, 1.4A (for the RPS-1000HV).
Figure 3.1 AC Power Connection
3.2 Battery Connection
The RPS-1000 battery charge capacity is 7.0 to 33.0 AH. Use 12V batteries of the same AH rating. Determine the correct AH rating as
per your current load calculation (see Table 2.4, Table 2.5 or Table 2.6).
To 120 VAC
Power Source
Wh
ite
Green
Bla
c
k
For RPS-1000
For RPS-1000HV
To 240 VAC
Power Source
Earth
(Ground)
Note: RPS-1000HV
models are labeled.
NOTE:
When your backup batteries requirements use backup batteries that are to large to fit into the RPS-1000 cabinet. The AB-33 cabinet
holds batteries up to the 33 AH size. (Refer to FACP Installation manual for AB-33 installation instructions.
Summary of Contents for Farenhyt RPS-1000
Page 49: ......