27
RPS-1000 / RPS-1000B Manual - P/N 151153:N 08/09/2017
Hardware Installation
Flexputs™ I/O Circuits
3.5.3 Conventional Initiation Circuits
This section of the manual explains how to install conventional initiating devices for Class A (Style D) or Class B (Style B) configura-
tions.
Class B Inputs
You can connect conventional Class B switches, such as waterflow switches and pull stations, directly to the I/O circuits of the RPS-
1000 panel.
To install a Class B switch:
1.
Wire the Class B switch as shown in Figure 3.10.
2.
Configure the circuit through programming (see
FACP Installation manual)
.
Figure 3.10 Class B Input Switches
Class A Inputs
You can connect conventional Class A switches, such as waterflow switches and pull stations, directly to the I/O circuits of the RPS-
1000 panel.
To install a Class A switch:
1.
Wire the Class A switch as shown in Figure 3.11.
2.
Configure the circuit through programming (see FACP Installation manual).
Figure 3.11 Class A initiating Switches
UL Listed EOL
4.7 k
Note:
I/O circuit 5 and 6
used as an example.
Any I/O point pairing
could be used.
NOTE:
In programming any point that uses multiple I/O circuits are always referred to as the lowest I/O circuit number used. For example,
Figure 3.11 uses both I/O circuit 5 and 6, so in programming it would be referred to as point 5
Summary of Contents for Farenhyt RPS-1000
Page 49: ......