Calculating Current Draw and Standby Battery
Addressable SLC Devices
IDP-Photo
Standby: .30 mA
1
mA
mA
IDP-Photo-T
mA
mA
IDP-PhotoR
mA
mA
IDP-Heat
mA
mA
IDP-Heat-HT
mA
mA
IDP-Acclimate
Standby: .30 mA
1
mA
mA
IDP-Heat-ROR
mA
mA
IDP-Beam (without integral test)
SLC
Standby/Alarm: 2 mA
mA
mA
Aux. Pwr
Standby: 2 mA
mA
Alarm: 8.5 mA
mA
IDP-Beam-T (with integral test)
SLC
Standby/Alarm: 2 mA
mA
mA
Aux. Pwr
Standby: 2 mA
mA
Alarm: 8.5 mA
mA
DNR
6
(non-relay)
None, included with IDP-PhotoR
DNR
7
(with relay)
None, included with IDP-PhotoR & IDP-Relay
IDP-CO-Fire
SLC
Standby: .30 mA
mA
Alarm: 7.2 mA
mA
IDP-Monitor
Standby/Alarm .375 mA
mA
mA
IDP-Minimon
mA
mA
IDP-Pull-SA/IDP-Pull-DA
mA
mA
IDP-Monitor-2
Standby/Alarm: .75 mA
mA
mA
IDP-Monitor-10
Standby/Alarm: 3.5 mA
mA
mA
IDP-Control
SLC
Standby .375 mA
mA
Alarm: .375 mA
mA
Aux Pwr
Standby 1.7 mA
mA
Alarm: 7mA
mA
IDP-Control-6
SLC
Standby 2.25 mA
mA
Alarm: 2.25 mA
mA
Aux Pwr
Standby 8 mA
mA
Alarm: 20 mA
mA
IDP-Relay
Standby/Alarm: .255 mA
mA
mA
IDP-Relay-6
Standby/Alarm: 1.45 mA
mA
mA
IDP-RelayMon-2
Standby: 1.3 mA
mA
Alarm: 24 mA
mA
IDP-Zone
Aux Pwr
Standby 12 mA
mA
Alarm: 90 mA
mA
SLC
Standby/Alarm .27 mA
mA
mA
IDP-Zone-6
Aux Pwr
Standby 50 mA
mA
Alarm: 70 mA
mA
SLC
Standby/Alarm 2 mA
mA
mA
SLC Accessories
B200SR Sounder Base
Aux Pwr
Standby: .5 mA
mA
Alarm: 35 mA
mA
SLC
Standby .3 mA
mA
B200S Intelligent Sounder Base
Aux Pwr
Standby: .5 mA
mA
Alarm: (high vol) 35 mA
mA
SLC
Standby .3 mA
mA
Table 2.4 Current Draw Worksheet for IDP SLC Devices
Device
# of Devices
Current per Device
Standby
Current
Alarm
Current
Summary of Contents for Farenhyt RPS-1000