RPS-1000 / RPS-1000B Manual - P/N 151153:N 08/09/2017
10
Calculating Current Draw and Standby Battery
Before You Begin Installing
B200SR-LF Low Frequency Sounder
Base
Aux Pwr
Standby: 1 mA
mA
Alarm: 125 mA
mA
B200S-LF Low Frequency Sounder
Base
Aux Pwr
Standby .55 mA
mA
Alarm (high vol) 140 mA
mA
SLC
Standby .30 mA
mA
B224RB Relay Base
Standby/Alarm: .5 mA
mA
mA
RT151/151 KEY
Alarm: 7.5 mA
mA
RA100Z
Alarm: 10 mA
mA
SLC Isolator Devices
IDP-ISO (Isolator Module)
Standby/Alarm: 0.45 mA
mA
mA
ISO-6 (6 Fault Isolator Module)
Standby: (per circuit) .45 mA
mA
Alarm: (per circuit) 17 mA
mA
B224BI Isolator Base
Standby/Alarm: 0.5 mA
mA
mA
Accessories Modules
6815 SLC Loop Expander
Standby: 78 mA
mA
Alarm: 78 mA
mA
RA-2000 Remote LCD Annunciator
Standby: 20 mA
mA
Alarm: 25 mA
mA
RA-1000 Remote LCD Annunciator
Standby: 20 mA
mA
Alarm: 25 mA
mA
RA-100 Remote LCD Annunciator
Standby: 25 mA
mA
Alarm: 50 mA
mA
5824 Serial/Parallel Module
Standby/Alarm: 45 mA
mA
mA
5496 NAC Expander
Standby/Alarm: 10 mA
mA
mA
RPS-1000 Power Supply
Standby/Alarm: 10 mA
mA
mA
5865-4 LED Annunciator
(with reset and silence switches)
Standby: 35 mA
mA
Alarm: 145 mA
mA
5865-3 LED Annunciator Module
Standby: 35 mA
mA
Alarm: 145 mA
mA
5880 LED I/O Module
Standby: 35 mA
mA
Alarm: 200 mA
mA
5883 Relay Interface
Standby: 0 mA
mA
Alarm: (22 mA/relay) 220 mA
mA
ESC-50W or ECS-125W Voice
Amplifier with/without ECS-CE4
Standby 10 mA
mA
Alarm 10 mA
mA
ECS-INT50W Internal Amplifier
Standby: 52 mA
mA
Alarm @ 25V: 275 mA
mA
Alarm @ 70V: 310 mA
mA
ECS-DUAL50W Dual Voice Amp
Standby/Alarm: 10 mA
mA
mA
ECS-50WBU Back-Up Amplifier
Standby/Alarm: 10 mA
mA
mA
ECS-VCM Voice Control Module
Standby: 70 mA
mA
Alarm: 100 mA
mA
ECS-NVCM Voice Control Module
Standby/Alarm: 59 mA
mA
mA
ECS-SW24 Switch Expander
Standby: 10 mA
mA
Alarm: 25 mA
mA
ECS-RPU Remote Paging Unit
Standby: 70 mA
mA
Alarm: 100 mA
mA
ECS-LOC Local Operating Console
(includes RA-2000, RVM & SW-24)
Standby: 105 mA
mA
Alarm: 175 mA
mA
Table 2.4 Current Draw Worksheet for IDP SLC Devices
Device
# of Devices
Current per Device
Standby
Current
Alarm
Current
Summary of Contents for Farenhyt RPS-1000