l
15 m (50 ft) example
l
X10 & .5ft/Div
l
30 dB & 9 dB Loss
l
Terminator connected
9. If…
any part of the return pulse is three (3) or more divisions from the base line (in either direction)…
Then…
the section of ControlNet trunk cable is Rejected.
If…
the return pulse is less than +/- three (3) divisions…
Then…
the section of ControlNet trunk cable is Accepted.
- 48 -
Chapter 6 - Testing ControlNet Trunk Cables