Fire Alarm Control Panel Compact
FB 798238.GB0 / 10.14
17
5.4 Type
menu
The desired zone type is selected in this menu.
A zone type is always assigned certain functions and parameters.
3
- overview compact
2 overview
3 select single assignment
- multiple assignment
zones
3
Select the desired zone from the list (1,2,3) -
(example with zone 0001)
1
3
type
1 fire
2 techn. alarm
3 pre-alarm
4 fault
5 control input
6 system input
7 unused
Fig. 27:
>Type< menu screen
The currently selected type is marked with a tick in the >Type<
sub-menu of a zone.
After a zone type has been selected, the program automatically
jumps to the sub-menu for the configuration of the selected zone
type.
This means that the zone menu and the possible setting options
change automatically according to the selected type.
Unused zones
The setting (if programmed) for zones with the >unused<
function type remains stored for any future applications.
Unused zones are not active. The wiring of the connection
terminals with a terminating element (EOL-I or 10K resistor) is
not necessary.
Selection
Type
Zone activation function
1
fire
The FACP buzzer will be activated and the “FIRE” LED goes on. All control
devices programmed as “FIRE” type will be activated. (ATU, alarm signalling
devices, etc.)
2 techn.
alarm
The FACP buzzer will be activated and the “TECH. ALARM” LED goes on. All
control devices programmed as “TAL” type will be activated. (ATU, Alarm
signalling devices, fire protection equipment will not be activated)
3
Pre-alarm
Die “Pre-Alarm” LED goes on. All control devices programmed as “Pre-Alarm”
type will be activated. (ATU, alarm signalling devices or fire protection equipment
will not be activated until the fire alarm condition (e.g. 2-zone dependency) is
fulfilled.)
4
fault
The FACP buzzer will be activated and the “FAULT” LED goes on. All control
devices programmed as “FAULT” type will be activated. (ATU, alarm signalling
devices, etc.)
5 control
input
One switching function will be executed when the zone is activated. 4 functions per
fire alarm zone can be executed for each “coming” and “going” activation.
6 system
input
A system state will be set on activation of the zone. Control functions that react to
this system state will be executed. The relating control zone must be defined
during the programming.
7
not used
Unused zones are not active. The settings (if programmed) are retained for later
activation. A wiring of the connection terminals with a termination element
(10K resistor or EOL-I) is not necessary.