Fire Alarm Control Panel Compact
40
FB 798238.GB0 / 10.14
8 Revision
menu
This function allows service work on the fire alarm control panel without triggering an external alerting.
1 information
2 overview
3 operate
4 service
5 revision
main menu
3
3
Select the >Revision< function with the
5
JKL
key.
3
revision
1 on
2 off
3
Fig. 61:
>Revision< menu screens
1
Press key
Revision ON
The ‘DISABLEMENT’ LED and the (yellow) LED for Fire Department alarm, Sounder and Fire
Protection Equipment (if a trigger prevention is programmed) blink on the control panel.
2
Press key
Revision off
The FACP is in normal mode again.
Only authorised and instructed persons may operate an installed and ready-for-alerting fire alarm
control panel and such persons must then operate the FACP in accordance with safety
precautions and, if applicable, the instruction of the emergency service (i.e. local fire brigade).
In the Revision mode, the Alarm Transmission Unit (ATU) and all other external alerting and fire
protection equipment may not be activated, depending on the configuration.