Fire Alarm Control Panel Compact
FB 798238.GB0 / 10.14
35
Delay on common fault in minutes
4
GHI
3
system timings 1/2
1 daylight saving time : on
2 daylight saving start: 25.03.12 02:00
3 daylight saving end : 28.10.12 02:00
4 delay common fault (min) : 15
5 delay mains fault (min) : 30
- sync. Bus alarm (s) : 0
- alarm suppression (s) : 000
Fig. 50: >Delay common fault< menu screen
A system common fault message will be suppressed for the set
time (00-99 minutes). No message display or activation will
occur during this time. The message will be displayed and the
assigned outputs activated if the fault cause still exists after the
set suppression time has elapsed.
“00” entry
no delay
Delay on mains failure in minutes
5
JKL
3
system timings 1/2
1 daylight saving time : on
2 daylight saving start: 25.03.12 02:00
3 daylight saving end : 28.10.12 02:00
4 delay common fault (min) : 15
5 delay mains fault (min) : 30
- sync. Bus alarm (s) : 0
- alarm suppression (s) : 000
Fig. 51: >Delay mains fault< menu screen
A mains supply fault will be suppressed for the set time
(00-99 minutes). This option is suitable for not displaying short-
term mains failures as a fault.
“00” entry
no delay
Observe standards and requirements!
Observe the information on the configuration and commissioning of the fire alarm control panel in
accordance with national standards/directives and local requirements.
This function may not be permissible or the programmable time may have to be set in accordance
with local requirements, depending on the specific use of the system or the country in which the
system is used.
Alarm suppression in seconds
3
system timings 1/2
1 daylight saving time : on
2 daylight saving start: 25.03.12 02:00
3 daylight saving end : 28.10.12 02:00
4 delay common fault (min) : 15
5 delay mains fault (min) : 30
- sync. Bus alarm (s) : 0
- alarm suppression (s) : 000
Fig. 52: >Alarm suppression< menu screen
If an alarm is detected during the 3 seconds shown here, after
a reset of the FACP, no alarm from the detector will be shown
on the control panel or analysed but instead only a pre-alarm.
save
entry
ESC
cancel entry or exit sub-menu