Fire Alarm Control Panel Compact
12
FB 798238.GB0 / 10.14
4.1 Event
log
Display of the event log
The event log can be displayed at access level 3. The last 10,000 events, such as alarm, fault, switch-off,
keyboard enable, are stored in the event log in chronological order. The last event is always displayed first.
The events are automatically assigned with a message serial number. A higher number therefore means a later
event (i.e. serial number 001 = oldest event).
3
service
1 event log
2 battery information
3 earth fault information
4 configuration
5 access level 4
- maintenance mode
Fig. 12:
>Service< menu screen
1
Select >Event log< menu item.
3
event log
3
1 Show
:
2 Time
: off
3 Object : All
4 Event
: 5/5
Fig. 13:
>event log< menu screen
The event display can be filtered by 'Time', 'Object' and 'Event'
here.
The event log can be searched for specific events with the cursor keys.
3
event no. : 01360
time : 09:58:06 19.06.2012
event : access level 3 com.
object : panel
label 1 :
label 2 :
add. info :
eventlog <-01360-> 01360
Fig. 14:
Event log menu and cursor keys
Fig. 15:
Cursor keys
Next 10 events (+10)
Next event (+1)
Previous 10 events (-10)
Previous event (-1)
Confirm selection/entry shown in the display