L7148F ELECTRONIC AQUASTAT

®

 CONTROLLER

Fig. 12. L7148F troubleshooting flowchart.

START
BOILER IS COLD.

BOILER IS NOT REACHING PROPER 
TEMPERATURE OR WILL NOT TURN ON.

CHECK:  L7148F DIAGNOSTIC LED ON?

CHECK FOR 120 VAC AT L1X, L2X.
CHECK FOR 24 VAC AT R, C.

TURN POWER ON;
CHECK ALL WIRING CONNECTIONS;
REPLACE TRANSFORMER AS APPROPRIATE.

SET ROOM THERMOSTAT AT 10 DEGREES
ABOVE ROOM TEMPERATURE.
SET BOILER 10 DEGREES (OR MORE)
ABOVE CURRENT WATER TEMPERATURE.
BOILER TURNS ON?

SHORT TERMINALS W-R (T-TW) ON  L7148F.
BOILER STARTS?

THERMOSTAT OR THERMOSTAT WIRING
PROBLEM. CHECK SYSTEM PER 
INSTRUCTIONS PROVIDED WITH THERMOSTAT.

NO

NO

YES

NO

YES

CHECK:  L7148F DIAGNOSTIC LED FLASHING?

TWO BLINKS:
CHECK SENSOR CONNECTIONS.
IF GOOD, REPLACE SENSOR.
THREE OR FOUR BLINKS:
INTERNAL ERROR, REPLACE L7148F.

L7148F IN RESET MODE (WAIT FIVE
MINUTES FOR CONTROL TO RESET). 
VENT DAMPER OPEN?

CHECK FOR 24V AT B1, B2.

YES

CHECK VENT DAMPER 
CABLE AND 
CONNECTIONS.
REPLACE VENT 
DAMPER CABLE OR 
DAMPER AS 
APPROPRIATE.

L7148F IS OKAY. 
CHECK IGNITION AND 
GAS VALVE SYSTEM 
AS DESCRIBED 
IN LITERATURE 
PROVIDED WITH 
THOSE PRODUCTS.

NO

YES

CHECK:  CIRCULATOR PUMP RUNNING?

YES

120 VAC AT C1, C2?

ROOM THERMOSTAT STILL SET 
10 DEGREES ABOVE CURRENT 
ROOM TEMPERATURE?

NO

BOILER SHUTS OFF AT 
HIGH LIMIT SETTING?

YES

NO

RESET THERMOSTAT AND 
REPEAT VOLTAGE CHECK.

REPLACE 
L7148F.

L7148F IS OKAY. CHECK OTHER SYSTEM 
COMPONENTS: CIRCULATOR. ZONE VALVES.

YES

YES

NO

BOILER SHUTS OFF ABOVE 
HIGH LIMIT SETTING?

NO

TRIADICATOR ACCURACY.
SENSOR FULLY INSERTED INTO WELL.
THERMO WELL IN GOOD CONDITION.
THERMO WELL LOCATED PER 
BOILER OEM INSTRUCTIONS.

YES

CHECK:
L7148F DIAGNOSTIC LED FLASHING?

NO
(BELOW HIGH LIMIT)

TWO BLINKS: REPLACE SENSOR.
THREE OR FOUR BLINKS: REPLACE L7148F.

YES

TRIADICATOR ACCURACY.
THERMO WELL LOCATED PER 
BOILER OEM INSTRUCTIONS.

NO

M20069

YES

NO

CHECK:

CHECK:

CHECK:

CHECK:

Summary of Contents for Electronic Aquastat L7148F

Page 1: ...ck connect or AMP plug connections T TV and Z terminals are provided in a terminal block with screw connections Vent damper plug optional Separate high limit control not required Software defined minimum maximum limit settings External 120 Vac to 24 Vac transformer ordered separately is field replaceable and upgradable Patented limit rated 209659A B C Sensors are separately replaceable Communicati...

Page 2: ...d feature modules L7148F Electronic Aquastat Controller with AMP plug connections with or without vent damper plug and communications port for adding advanced feature modules AMP connector on wiring board for transformer connection High Limit Setpoint Range 130 F to 240 F 54 C to 116 C Select models may be different Differential Fixed 10 F 6 C Select models may be different Operating Voltage Range...

Page 3: ...om of well IMPORTANT The L7148F is not designed for spud mounting to the sensing well Sensor and immersion well are not provided and must be purchased separately Mounting screws must be obtained locally See Table 1 for sensor specifications The sensor is adaptable to existing immersion wells with a shell I D of 3 8 in 10 mm To order an immersion well contact your distributor or Honeywell sales rep...

Page 4: ...tions 1 Strip 1 16 in of insulation from the wire end 2 Insert the wire under the terminal screw and contact plate 3 Using a standard flat headed screwdriver tighten the screw until the wire is firmly in contact with the screw and contact plate 4 Tighten the screw an additional one half turn For quick connect terminal connections Connect the quick connect to the appropriate terminal on the control...

Page 5: ...l exits the high limit state and returns to the normal state when the temperature of the boiler drops to the high limit setting minus 10 F 12 C 3 Reset Detects an error condition such as an open sensor and shuts down all outputs The control continues to function and automatically restarts if the error condition is corrected High Limit The high limit switch shuts off the burner B1 B2 output when th...

Page 6: ...ON B1 AND S1 ARE 3 16 INCH QUICK CONNECT TERMINALS ALL OTHER TERMINALS ARE 1 4 INCH C COM Z B2 G ARE ALL CONNECTED INSIDE DEVICE R IS A CONVENIENCE TERMINAL FOR 24V HOT CONNECTION FOR USE WITH IGNITION CONTROLS 1 2 3 4 5 6 7 M11475B L1 HOT L2 1 4 3 TR TH TH TR T87F ZONE 3 T87F ZONE 2 T87F ZONE 1 END SWITCH V8043F 3 TR TH TH TR END SWITCH V8043F 3 TR TH TH TR END SWITCH V8043F COM L7148F HIGH LIMIT...

Page 7: ... 2 L1 L2 DISCONNECT SWITCH 1 6 TO ADVANCED FEATURE MODULE TO BOILER SENSOR 24V COM L2X L1X C R 5 OPTIONAL VENT DAMPER PLUG C1 G L1 C2 L2X L1X B2 B1 R C R DATA PORT STATUS THERMOSTAT C W R S1 S2 4 4 4 4 4 3 3 TR TH THTR LOW VOLTAGE GAS VALVE VR8300 L1 HOT L2 1 1 2 2 3 3 4 4 4 4 3 4 5 6 5 1 2 4 6 POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED GROUND MUST BE AN EARTH GROUND...

Page 8: ...ENSOR 120V L2X L1X C R 3 OPTIONAL VENT DAMPER PLUG COM BURNER CONTROL 24V HOT TO VALVE OR IGNITION CONTROL C1 G L1 C2 L2 L2X L1X B2 B1 R C R DATA PORT STATUS THERMOSTAT C W R S1 S2 5 5 5 5 5 4 4 L1 HOT L2 1 1 2 3 1 2 3 1 2 3 1 2 3 CIRCULATOR POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED GROUND MUST BE AN EARTH GROUND CONNECTION B1 AND S1 ARE 3 16 INCH QUICK CONNECT TERM...

Page 9: ...NT DAMPER IS PLUGGED INTO L7148F FUSE BLOWS WHEN THERMOSTAT FIRST CLOSES AFTER FUSE BLOWS L7148F OPERATES ONLY WHEN VENT DAMPER IS CONNECTED SEE VENT DAMPER PRODUCT SPECIFICATIONS FOR INTERNAL SCHEMATICS S1 IS A 3 16 INCH QUICK CONNECT TERMINAL S2 IS 1 4 INCH THIS DEVICE HAS AMP PLUGS C COM Z B2 G ARE ALL CONNECTED INSIDE DEVICE FOR EXTERNAL TRANSFORMER VA REQUIREMENTS REFER TO APPLICATION SECTION...

Page 10: ...NS AND OVERLOAD PROTECTION AS REQUIRED GROUND MUST BE AN EARTH GROUND CONNECTION FOR EXTERNAL TRANSFORMER VA REQUIREMENTS REFER TO APPLICATION SECTION R882C IS PROVIDED WITH NEC CLASS 1 ENCLOSURE B1 AND S1 ARE 3 16 INCH QUICK CONNECT TERMINALS ALL OTHER TERMINALS ARE 1 4 INCH C COM Z B2 G ARE ALL CONNECTED INSIDE DEVICE R IS A CONVENIENCE TERMINAL FOR 24V HOT CONNECTION FOR USE WITH IGNITION CONTR...

Page 11: ...REQUIRED GROUND MUST BE AN EARTH GROUND CONNECTION B1 AND S1 ARE 3 16 INCH QUICK CONNECT TERMINALS ALL OTHER TERMINALS ARE 1 4 INCH C Z B2 G ARE ALL CONNECTED INSIDE DEVICE FOR EXTERNAL TRANSFORMER VA REQUIREMENTS REFER TO APPLICATION SECTION R IS A CONVENIENCE TERMINAL FOR 24V HOT CONNECTION FOR USE WITH IGNITION CONTROLS 1 2 3 4 5 6 M11479B 24 VOLT COMMON 24 VOLT HOT EFT OUTPUT 24 VOLT THERMOSTA...

Page 12: ... STARTS THERMOSTAT OR THERMOSTAT WIRING PROBLEM CHECK SYSTEM PER INSTRUCTIONS PROVIDED WITH THERMOSTAT NO NO YES NO YES CHECK L7148F DIAGNOSTIC LED FLASHING TWO BLINKS CHECK SENSOR CONNECTIONS IF GOOD REPLACE SENSOR THREE OR FOUR BLINKS INTERNAL ERROR REPLACE L7148F L7148F IN RESET MODE WAIT FIVE MINUTES FOR CONTROL TO RESET VENT DAMPER OPEN CHECK FOR 24V AT B1 B2 YES CHECK VENT DAMPER CABLE AND C...