L7148F ELECTRONIC AQUASTAT

®

 CONTROLLER

68-0189—2

2

ORDERING INFORMATION

When purchasing replacement and modernization products from your TRADELINE® wholesaler or distributor, refer to the 

TRADELINE® Catalog or price sheets for complete ordering number.

If you have additional questions, need further information, or would like to comment on our products or services, please write or 

phone:

1.

Your local Home and Building Control Sales Office (check white pages of your phone directory).

2.

Home and Building Control Customer Relations

Honeywell, 1885 Douglas Drive North

Minneapolis, Minnesota 55422-4386 

In Canada—Honeywell Limited/Honeywell Limitée, 35 Dynamic Drive, Scarborough, Ontario M1V 4Z9.

International Sales and Service Offices in all principal cities of the world. Manufacturing in Australia, Canada, Finland, France, 

Germany, Japan, Mexico, Netherlands, Spain, Taiwan, United Kingdom, U.S.A.

SPECIFICATIONS

IMPORTANT

The specifications given in this publication do 

not include normal manufacturing tolerances. 

Therefore, this unit may not exactly match the 
listed specifications. Also, this product is tested 

and calibrated under closely controlled conditions, 

and some minor differences in performance can be 
expected if those conditions are changed.

Standard Models

Models:

L7148F Electronic Aquastat Controller with quick 

connect terminals, with or without vent damper plug 

and communications port (for adding advanced feature 
modules).

L7148F Electronic Aquastat Controller with AMP plug 

connections, with or without vent damper plug and 
communications port (for adding advanced feature 

modules). AMP connector on wiring board for 

transformer connection.

High Limit Setpoint Range:  

130°F to 240°F 

(54°C to 116°C). (Select models may be different.)

Differential:  

Fixed 10°F (6°C). (Select models may 

be different.)

Operating Voltage Range:

L1-L2 Line Voltage Power: Nominal, 120 Vac.
R-C 24V Transformer Output: Nominal, 24 Vac.

Minimum/Maximum Ambient Temperature:

-30°F (-9°C) with 2.0A 24V load.

150°F (66°C) with 2.0A 24V load. 

Operating Relative Humidity: 

0 to 95% RH non-condensing.

Electrical Ratings (60 Hz only):

B1-B2: 2.0A at 24 Vac.

C1-C2: Full Load 7.4A at 120 Vac; Locked Rotor, 

44.4A at 120 Vac.

NOTE: Total Low Voltage load must not exceed 4.0A.

Case Dimensions: 

See Fig. 1.

Fig. 1. L7148F dimensions in in. (mm).

Mounting: 

Vestibule mount.

Approvals:

Underwriters Laboratories Inc. Component Recognized: 

File No. MP466.

Canadian Underwriters Laboratories Inc. Component 

Recognized: File No. MP466.

ANSI Miswiring: 3/16 in. (5 mm) B1 quick connect terminal 

and AMP® plug connections meet ANSI Appliance 
Miswiring Standard.

Material Safety Data Sheets (MSDS): 

For more information 

on heat-conductive compound, see form 69-0955.

Accessories:

107408 Heat Conductive Compound (4 oz. can). For more 

information, see form 69-0955, Heat Conductive 

Compound.

121371AA Sensor Retaining Clamp.

32002656-001 Sensor Retaining Spring.

Sensor: 

Sensor available separately. For leadwire lengths 

available, see Table 1.

7/16 (11)

1-3/16

(30)

4-1/2
(114)

6

(152)

3/8

(10)

4-11/16 (119)

4 (102)

5/8

(16)

1-5/8

(41)

M11500

1/2

(13)

Summary of Contents for Electronic Aquastat L7148F

Page 1: ...ck connect or AMP plug connections T TV and Z terminals are provided in a terminal block with screw connections Vent damper plug optional Separate high limit control not required Software defined minimum maximum limit settings External 120 Vac to 24 Vac transformer ordered separately is field replaceable and upgradable Patented limit rated 209659A B C Sensors are separately replaceable Communicati...

Page 2: ...d feature modules L7148F Electronic Aquastat Controller with AMP plug connections with or without vent damper plug and communications port for adding advanced feature modules AMP connector on wiring board for transformer connection High Limit Setpoint Range 130 F to 240 F 54 C to 116 C Select models may be different Differential Fixed 10 F 6 C Select models may be different Operating Voltage Range...

Page 3: ...om of well IMPORTANT The L7148F is not designed for spud mounting to the sensing well Sensor and immersion well are not provided and must be purchased separately Mounting screws must be obtained locally See Table 1 for sensor specifications The sensor is adaptable to existing immersion wells with a shell I D of 3 8 in 10 mm To order an immersion well contact your distributor or Honeywell sales rep...

Page 4: ...tions 1 Strip 1 16 in of insulation from the wire end 2 Insert the wire under the terminal screw and contact plate 3 Using a standard flat headed screwdriver tighten the screw until the wire is firmly in contact with the screw and contact plate 4 Tighten the screw an additional one half turn For quick connect terminal connections Connect the quick connect to the appropriate terminal on the control...

Page 5: ...l exits the high limit state and returns to the normal state when the temperature of the boiler drops to the high limit setting minus 10 F 12 C 3 Reset Detects an error condition such as an open sensor and shuts down all outputs The control continues to function and automatically restarts if the error condition is corrected High Limit The high limit switch shuts off the burner B1 B2 output when th...

Page 6: ...ON B1 AND S1 ARE 3 16 INCH QUICK CONNECT TERMINALS ALL OTHER TERMINALS ARE 1 4 INCH C COM Z B2 G ARE ALL CONNECTED INSIDE DEVICE R IS A CONVENIENCE TERMINAL FOR 24V HOT CONNECTION FOR USE WITH IGNITION CONTROLS 1 2 3 4 5 6 7 M11475B L1 HOT L2 1 4 3 TR TH TH TR T87F ZONE 3 T87F ZONE 2 T87F ZONE 1 END SWITCH V8043F 3 TR TH TH TR END SWITCH V8043F 3 TR TH TH TR END SWITCH V8043F COM L7148F HIGH LIMIT...

Page 7: ... 2 L1 L2 DISCONNECT SWITCH 1 6 TO ADVANCED FEATURE MODULE TO BOILER SENSOR 24V COM L2X L1X C R 5 OPTIONAL VENT DAMPER PLUG C1 G L1 C2 L2X L1X B2 B1 R C R DATA PORT STATUS THERMOSTAT C W R S1 S2 4 4 4 4 4 3 3 TR TH THTR LOW VOLTAGE GAS VALVE VR8300 L1 HOT L2 1 1 2 2 3 3 4 4 4 4 3 4 5 6 5 1 2 4 6 POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED GROUND MUST BE AN EARTH GROUND...

Page 8: ...ENSOR 120V L2X L1X C R 3 OPTIONAL VENT DAMPER PLUG COM BURNER CONTROL 24V HOT TO VALVE OR IGNITION CONTROL C1 G L1 C2 L2 L2X L1X B2 B1 R C R DATA PORT STATUS THERMOSTAT C W R S1 S2 5 5 5 5 5 4 4 L1 HOT L2 1 1 2 3 1 2 3 1 2 3 1 2 3 CIRCULATOR POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED GROUND MUST BE AN EARTH GROUND CONNECTION B1 AND S1 ARE 3 16 INCH QUICK CONNECT TERM...

Page 9: ...NT DAMPER IS PLUGGED INTO L7148F FUSE BLOWS WHEN THERMOSTAT FIRST CLOSES AFTER FUSE BLOWS L7148F OPERATES ONLY WHEN VENT DAMPER IS CONNECTED SEE VENT DAMPER PRODUCT SPECIFICATIONS FOR INTERNAL SCHEMATICS S1 IS A 3 16 INCH QUICK CONNECT TERMINAL S2 IS 1 4 INCH THIS DEVICE HAS AMP PLUGS C COM Z B2 G ARE ALL CONNECTED INSIDE DEVICE FOR EXTERNAL TRANSFORMER VA REQUIREMENTS REFER TO APPLICATION SECTION...

Page 10: ...NS AND OVERLOAD PROTECTION AS REQUIRED GROUND MUST BE AN EARTH GROUND CONNECTION FOR EXTERNAL TRANSFORMER VA REQUIREMENTS REFER TO APPLICATION SECTION R882C IS PROVIDED WITH NEC CLASS 1 ENCLOSURE B1 AND S1 ARE 3 16 INCH QUICK CONNECT TERMINALS ALL OTHER TERMINALS ARE 1 4 INCH C COM Z B2 G ARE ALL CONNECTED INSIDE DEVICE R IS A CONVENIENCE TERMINAL FOR 24V HOT CONNECTION FOR USE WITH IGNITION CONTR...

Page 11: ...REQUIRED GROUND MUST BE AN EARTH GROUND CONNECTION B1 AND S1 ARE 3 16 INCH QUICK CONNECT TERMINALS ALL OTHER TERMINALS ARE 1 4 INCH C Z B2 G ARE ALL CONNECTED INSIDE DEVICE FOR EXTERNAL TRANSFORMER VA REQUIREMENTS REFER TO APPLICATION SECTION R IS A CONVENIENCE TERMINAL FOR 24V HOT CONNECTION FOR USE WITH IGNITION CONTROLS 1 2 3 4 5 6 M11479B 24 VOLT COMMON 24 VOLT HOT EFT OUTPUT 24 VOLT THERMOSTA...

Page 12: ... STARTS THERMOSTAT OR THERMOSTAT WIRING PROBLEM CHECK SYSTEM PER INSTRUCTIONS PROVIDED WITH THERMOSTAT NO NO YES NO YES CHECK L7148F DIAGNOSTIC LED FLASHING TWO BLINKS CHECK SENSOR CONNECTIONS IF GOOD REPLACE SENSOR THREE OR FOUR BLINKS INTERNAL ERROR REPLACE L7148F L7148F IN RESET MODE WAIT FIVE MINUTES FOR CONTROL TO RESET VENT DAMPER OPEN CHECK FOR 24V AT B1 B2 YES CHECK VENT DAMPER CABLE AND C...