L7148F ELECTRONIC AQUASTAT

®

 CONTROLLER

68-0189—2

4

IMPORTANT

• Sensor must be fully inserted to bottom of well.
• Remove all heat conductive compound from the well 

prior to sensor insertion.

5.

Insert the sensor into the well. Make sure the sensor fits 

securely against the bottom of the well.

To secure sensor and leadwire with mounting clamp 

(see Fig. 2.):

1.

Loosen the draw nut and spread the jaws of the clamp.

2.

Slide the jaws of the clamp over the mounting flange.

3.

Adjust the sensor leadwire to fit through the groove in 

the mounting clamp.

IMPORTANT

Do not overtighten the draw nut or a system 
shut-down could occur.

4.

Tighten the draw nut so that the clamp is firmly attached 
to the well and the leadwire is held securely in place.

5.

Secure excess leadwire to prevent disconnection of 

sensor or removal from the well.

Fig. 2. Secure sensor and leadwire with mounting 

clamp or spring (see Accessories).

Wiring

WARNING

Electrical shock hazard.
Can cause serious injury, death or equipment 

damage.

Disconnect power supply before beginning wiring. 

IMPORTANT

• An external transformer is required for operation. 

The user must size the transformer for the specific 

application.

• If L7148F is used to power zone valves, total low 

voltage (24V) load must not exceed 4A. Use a 

zoning panel such as the Honeywell R8889 when 

load exceeds these ratings.

All wiring must comply with local electrical codes and 

ordinances. Refer to the SPECIFICATIONS section when 
applying this control. For appropriate wiring diagrams, see 

Fig. 3 through 10.

For screw terminal connections:

1.

Strip 1/16 in. of insulation from the

 wire end.

2.

Insert the wire under the terminal 

screw and contact plate.

3.

Using a standard, flat-headed 
screwdriver, tighten the screw until 

the wire is firmly in contact with the 

screw and contact plate.

4.

Tighten the screw an additional 

one-half turn.

For quick connect terminal connections:

Connect the quick connect to the appropriate terminal on 

the control. B1 and S1 are 3/16 in. (5 mm) quick connect 
terminals; all other terminals are 1/4 in. (6 mm). 

For AMP plug connections:
Connect the AMP plugs to the receptacles on the control. 

An AMP plug connection is shown in Fig. 8.

The L7148F and appropriately sized external transformer can 

power up to three Honeywell V8043 Zone Valves. Additional 
valves, in groups of three or less, require an additional 

transformer, or use Honeywell R8889 Zone Valve Panel. 

Follow the appropriate wiring diagrams when using zone 
valves. See Fig. 4, 5, 7, and 9.

On systems requiring a vent damper, the Honeywell vent 
damper can be connected directly to some L7148F Electronic 

Aquastat models (Fig. 9) or S8610 Spark Ignition Modules 

(Fig.8). With the vent damper plugged into the Electronic 
Aquastat Controller, a fuse in the Electronic Aquastat 

Controller  blows when the thermostat first closes. Once 

the fuse is blown, the Electronic Aquastat Controller does 
not operate unless the vent damper is connected. With the 

vent damper plugged into the S8610, a fuse in the ignition 

module blows when first powered. Once the fuse is blown, 
the ignition module does not operate unless the vent damper 

is connected.

JAWS OF 
CLAMP

CLAMP

SENSOR
LEADWIRE

SENSOR

MOUNTING
FLANGE

PLACE

JAWS OF 

CLAMP OVER 

MOUNTING FLANGE

TIGHTEN SCREW AND DRAW NUT
TO SECURE CLAMP

M11483

BOTTOM OF WELL

M11484

Summary of Contents for Electronic Aquastat L7148F

Page 1: ...ck connect or AMP plug connections T TV and Z terminals are provided in a terminal block with screw connections Vent damper plug optional Separate high limit control not required Software defined minimum maximum limit settings External 120 Vac to 24 Vac transformer ordered separately is field replaceable and upgradable Patented limit rated 209659A B C Sensors are separately replaceable Communicati...

Page 2: ...d feature modules L7148F Electronic Aquastat Controller with AMP plug connections with or without vent damper plug and communications port for adding advanced feature modules AMP connector on wiring board for transformer connection High Limit Setpoint Range 130 F to 240 F 54 C to 116 C Select models may be different Differential Fixed 10 F 6 C Select models may be different Operating Voltage Range...

Page 3: ...om of well IMPORTANT The L7148F is not designed for spud mounting to the sensing well Sensor and immersion well are not provided and must be purchased separately Mounting screws must be obtained locally See Table 1 for sensor specifications The sensor is adaptable to existing immersion wells with a shell I D of 3 8 in 10 mm To order an immersion well contact your distributor or Honeywell sales rep...

Page 4: ...tions 1 Strip 1 16 in of insulation from the wire end 2 Insert the wire under the terminal screw and contact plate 3 Using a standard flat headed screwdriver tighten the screw until the wire is firmly in contact with the screw and contact plate 4 Tighten the screw an additional one half turn For quick connect terminal connections Connect the quick connect to the appropriate terminal on the control...

Page 5: ...l exits the high limit state and returns to the normal state when the temperature of the boiler drops to the high limit setting minus 10 F 12 C 3 Reset Detects an error condition such as an open sensor and shuts down all outputs The control continues to function and automatically restarts if the error condition is corrected High Limit The high limit switch shuts off the burner B1 B2 output when th...

Page 6: ...ON B1 AND S1 ARE 3 16 INCH QUICK CONNECT TERMINALS ALL OTHER TERMINALS ARE 1 4 INCH C COM Z B2 G ARE ALL CONNECTED INSIDE DEVICE R IS A CONVENIENCE TERMINAL FOR 24V HOT CONNECTION FOR USE WITH IGNITION CONTROLS 1 2 3 4 5 6 7 M11475B L1 HOT L2 1 4 3 TR TH TH TR T87F ZONE 3 T87F ZONE 2 T87F ZONE 1 END SWITCH V8043F 3 TR TH TH TR END SWITCH V8043F 3 TR TH TH TR END SWITCH V8043F COM L7148F HIGH LIMIT...

Page 7: ... 2 L1 L2 DISCONNECT SWITCH 1 6 TO ADVANCED FEATURE MODULE TO BOILER SENSOR 24V COM L2X L1X C R 5 OPTIONAL VENT DAMPER PLUG C1 G L1 C2 L2X L1X B2 B1 R C R DATA PORT STATUS THERMOSTAT C W R S1 S2 4 4 4 4 4 3 3 TR TH THTR LOW VOLTAGE GAS VALVE VR8300 L1 HOT L2 1 1 2 2 3 3 4 4 4 4 3 4 5 6 5 1 2 4 6 POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED GROUND MUST BE AN EARTH GROUND...

Page 8: ...ENSOR 120V L2X L1X C R 3 OPTIONAL VENT DAMPER PLUG COM BURNER CONTROL 24V HOT TO VALVE OR IGNITION CONTROL C1 G L1 C2 L2 L2X L1X B2 B1 R C R DATA PORT STATUS THERMOSTAT C W R S1 S2 5 5 5 5 5 4 4 L1 HOT L2 1 1 2 3 1 2 3 1 2 3 1 2 3 CIRCULATOR POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED GROUND MUST BE AN EARTH GROUND CONNECTION B1 AND S1 ARE 3 16 INCH QUICK CONNECT TERM...

Page 9: ...NT DAMPER IS PLUGGED INTO L7148F FUSE BLOWS WHEN THERMOSTAT FIRST CLOSES AFTER FUSE BLOWS L7148F OPERATES ONLY WHEN VENT DAMPER IS CONNECTED SEE VENT DAMPER PRODUCT SPECIFICATIONS FOR INTERNAL SCHEMATICS S1 IS A 3 16 INCH QUICK CONNECT TERMINAL S2 IS 1 4 INCH THIS DEVICE HAS AMP PLUGS C COM Z B2 G ARE ALL CONNECTED INSIDE DEVICE FOR EXTERNAL TRANSFORMER VA REQUIREMENTS REFER TO APPLICATION SECTION...

Page 10: ...NS AND OVERLOAD PROTECTION AS REQUIRED GROUND MUST BE AN EARTH GROUND CONNECTION FOR EXTERNAL TRANSFORMER VA REQUIREMENTS REFER TO APPLICATION SECTION R882C IS PROVIDED WITH NEC CLASS 1 ENCLOSURE B1 AND S1 ARE 3 16 INCH QUICK CONNECT TERMINALS ALL OTHER TERMINALS ARE 1 4 INCH C COM Z B2 G ARE ALL CONNECTED INSIDE DEVICE R IS A CONVENIENCE TERMINAL FOR 24V HOT CONNECTION FOR USE WITH IGNITION CONTR...

Page 11: ...REQUIRED GROUND MUST BE AN EARTH GROUND CONNECTION B1 AND S1 ARE 3 16 INCH QUICK CONNECT TERMINALS ALL OTHER TERMINALS ARE 1 4 INCH C Z B2 G ARE ALL CONNECTED INSIDE DEVICE FOR EXTERNAL TRANSFORMER VA REQUIREMENTS REFER TO APPLICATION SECTION R IS A CONVENIENCE TERMINAL FOR 24V HOT CONNECTION FOR USE WITH IGNITION CONTROLS 1 2 3 4 5 6 M11479B 24 VOLT COMMON 24 VOLT HOT EFT OUTPUT 24 VOLT THERMOSTA...

Page 12: ... STARTS THERMOSTAT OR THERMOSTAT WIRING PROBLEM CHECK SYSTEM PER INSTRUCTIONS PROVIDED WITH THERMOSTAT NO NO YES NO YES CHECK L7148F DIAGNOSTIC LED FLASHING TWO BLINKS CHECK SENSOR CONNECTIONS IF GOOD REPLACE SENSOR THREE OR FOUR BLINKS INTERNAL ERROR REPLACE L7148F L7148F IN RESET MODE WAIT FIVE MINUTES FOR CONTROL TO RESET VENT DAMPER OPEN CHECK FOR 24V AT B1 B2 YES CHECK VENT DAMPER CABLE AND C...

Reviews: