L7148F ELECTRONIC AQUASTAT
®
CONTROLLER
68-0189—2
6
Table 2. Sequence of Operation
Fig. 4. Wiring L7148F with multizone valves.
Thermostat
Operation
Mode
Burner
Circulator
Off
Normal
Off
Off
Off
High Limit
Off
Off
On
Normal
On
On
On
High Limit
Off
On
Either
Reset
Off
Off
POWER SUPPLY. PROVIDE DISCONNECT MEANS
AND OVERLOAD PROTECTION AS REQUIRED.
GROUND MUST BE AN EARTH GROUND CONNECTION.
ADD JUMPER AS SHOWN.
FOR EXTERNAL TRANSFORMER VA REQUIREMENTS,
REFER TO APPLICATION SECTION.
B1 AND S1 ARE 3/16 INCH. QUICK CONNECT TERMINALS.
ALL OTHER TERMINALS ARE 1/4 INCH.
C, COM, Z, B2, G ARE ALL CONNECTED INSIDE DEVICE.
R IS A CONVENIENCE TERMINAL FOR 24V HOT
CONNECTION FOR USE WITH IGNITION CONTROLS.