Main Menu - User Programming
Programming
NAC Options
NAC Type
The NAC circuit can be programmed to activate for specific applications. Select
Mass
Notification
to turn on the NAC circuit only for a mass notification event,
Fire Evacuation
to turn
on the NAC circuit only for a fire evacuation event,
Both
to turn on the NAC circuit for both mass
notification and fire evacuation events, or
Follow Input
to have the NAC follow the input from an
external source (connections to TB18). To use
Both,
the Unit Operation must be set to Combina-
tion. Refer to “Unit Operation” on page 61.
NAC Protocol
The programmer can select the notification appliance coding or strobe synchroni-
zation by selecting the corresponding drop-down box. Select
System Sensor
for System Sensor syn-
chronization,
Wheelock
, for Wheelock synchronization,
Gentex
for Gentex synchronization, or
Steady
, for a continuous output with no coding.
To ensure proper strobe and circuit operation, there is also a limit to the number of strobes that can
be attached to each circuit. Following is a list of the strobes that have been tested with the ECC and
the maximum number that can be connected to each NAC. Make sure that the NAC maximum cur-
rent is not exceeded.
Aux Power
Selects whether this power is
Constant
or
Resettable
use from TB17.
Speaker Volume Control NAC
If the Cooper Wheelock SP-SVC module is installed on TB23
of the main control board, allowing manual volume setting for telephone paging and background
music for a specific speaker or speaker zone, select
Enabled
.
Console Control
Console Priority
Priority can be assigned to the operator consoles so that the primary operator
interface can always override the functions at the local operator consoles or remote microphones.
Select
POC->LOC->RM
for console priority. Selecting
Equal
for priority allows users with access
to the system on a a “first come, first served” basis.
Strobe Manufacturer
Maximum Number of Strobes
System Sensor
31
Wheelock
34
Gentex
26
Table 3.1 Maximum Number of Strobes by Manufacturer
Figure 3.4 NAC Options
n
a
c
o
p
ti
o
n
s
2
.j
p
g
Figure 3.5 Console Control
c
o
n
s
o
le
c
o
n
tr
o
l2
.j
p
g
Summary of Contents for ECC-50/100
Page 83: ...Emergency Command Center Manual P N LS10001 000FL E G 5 3 2016 83 Notes ...
Page 95: ...Emergency Command Center Manual P N LS10001 000FL E G 5 3 2016 95 Notes ...
Page 102: ...102 Emergency Command Center Manual P N LS10001 000FL E G 5 3 2016 Notes ...
Page 106: ...106 Emergency Command Center Manual P N LS10001 000FL E G 5 3 2016 Slide in Labels ...
Page 108: ...108 Emergency Command Center Manual P N LS10001 000FL E G 5 3 2016 Slide in Labels ...
Page 114: ...Cut along dotted line ...