   DFS8M 

- Installation Instructions

 

Wireless Smoke Sensor with sounder

 

 
 

Registration

 

Registration  is the  procedure  associating the DFS8M to the  control 
panel. This operation requires a programming  tool. The complete 
procedure  is described  in the  alarm  central  unit installation manual  or in 
the programming  tool manual.  Bellow are listed the main  steps  of the 
registration  procedure:

 

1. Connect  the  programming  tool and start programming

 

2. Go to the 

„REGISTER‟ menu

 

3. Press  the R adio button (see figure  2) or the Test&Hush (see figure  4) 
on the device when prompted by the programming  tool. The panel  will 
emit  a confirmation beep. 

Warning: The detector plays fire siren.

 

4. Choose  the operating mode  and enter the label

 

5. Exit programming  mode

 

 

Note: The detector must  always be programmed  in  its  final  location  with 
a minimum radio level of 3 units on a scale  of 10

 

 

Manually Testing your Smoke Detector

 

 

It  is  recommended  to  test  the  smoke  alarm  after  installation  and  then  at 
least  weekly  to  ensure the  units are  working. Press  and hold the 

“Test & 

Hush” button until the Alarm sounds and the red light flashes (see Figure 
4). The Alarm will stop sounding shortly after the button is released.

 

 

WARNING  1:  Do  not  test  with  flame.  This  can  set  fire  to  the Alarm 
and  damage  the  house.  We  do  not  recommend  testing  with  smoke 
as the results can be misleading unless special apparatus is used. 
 
WARNING 2: Do protect your ears during the test.

 

 

“Test & Hush” button to Control Nuisance Alarms

 

The  DFS8M  has  a  combined 

“Test  &  Hush”  button  to  help  you  control 

nuisance/false alarms.

 

1. To cancel a false alarm, press the 

“Test & Hush” button (the sensor will 

automatically switch to a reduced sensitivity condition). It will be silenced 
for a period of approximately 10 minutes. The red light on the cover of the 
Smoke  Alarm  will  flash  every  10  seconds  (instead  of  40  seconds)  to 
indicate that the unit has been silenced.

 

2.  The  device  will  reset  to  normal  sensitivity  at  the  end  of  the  silenced 
period  (10  minutes).  If  additional  silenced  time  is  required,  simply  push 
the 

“Test & Hush” button again.

 

 

Battery Replacement

 

A  fresh  Alkaline  Battery  should  last  for  over  a  year.  When  the  battery 
power is low and replacement is necessary the smoke alarm will signal it 
to the  panel  and locally: 

the  device  will “beep”  and the  red light  will  flash 

at the same time about once per minute for at least 30 days. The battery 
must  then  be  replaced.  Also,  replace  the  battery  if  the  Alarm  does  not 
sound when the 

“Test & Hush” button is pressed. For maximum reliability, 

replace  the  battery  at  least  once  a  year.  When  you  replace  the  battery 
you  must  press  the 

“Test  &  Hush”  button  to  check  that  the  Alarm  is 

functioning  correctly.  Only  replace  the  battery  with  one  of  the  following 
alkaline  batteries:  Duracell  MN1604,  Energizer  6LR61,  Philips  6LR61, 
Varta 6LR61 or the Ultralife U9VL-J lithium battery. The lithium battery will 
last longer than an alkaline battery.

 

Note: Prolonged  exposure  to  low  or  high  temperatures  or  high  humidity 
may  reduce  battery  life.  Prolonged  periods  of  alarm  will  also  reduce 
battery life.

 

 

BATTERY  REMOVAL  AND  HANDLING  SAFETY  WARNING:  Risk  of  fire,  explosion 
and  burns,  do  not  recharge,  disassemble,  heat  above  100°  C,  or  incinerate  the  bat -  tery. 
While the battery can normally be safely removed by hand, care should be used to ensure 
that the  battery  terminals are  not  shorted,  nor the  battery  damaged,  during the  removal 
process.  Dispose  of depleted  batteries  by  complying  with  applicable  national  and  local 
regulations. In the event of the battery being damaged, use personal protective equipment 
to  remove  it  immediately,  and  dispose  of  it  in  a  safe  manner  (refer  to  the  battery 
manufacturer’s specifications for such situations).

 

 

Maintenance

 

Clean  the  smoke  head  regularly.  Use  a  soft  bristle  brush  or  the  brush 
attachment of your vacuum cleaner to remove dust and cobwebs from the 
side slots  where the smoke/heat  enters. To clean the cover,  wipe  with  a 
damp cloth and dry thoroughly.

 

 
 
 

2011 Honeywell  International  Inc.

 

 

The smoke  chamber  in  the  smoke  head  automatically  tests  itself  every 40 
seconds.  If  the  chamber  is  degraded  it  will  beep  without  the  red  light 
flashing  at  the  same time.  If  this  happens  clean  the  unit.  If  the  beeping 
persists  and  the  beep does  not  coincide  with  a  red light  flash,  return  the 
unit.

 

 

Smoke  sensors and particularly the  optical (photoelectric)  type  are prone 
to dust and insect ingress  which can cause false alarms.

 

 

The latest design, materials and manufacturing techniques have been used 
in the construction  of this product to  minimise the  effects  of contamination. 
However  it  is  impossible  to  completely  eliminate  the  effect  of  dust  and 
insect  contamination,  and  therefore,  to  prolong  the  life  of  the  Alarm  you 
must ensure that it is kept clean so that excess dust does not build up. Any 
insects  or  cobwebs  in  the  vicinity  of  the  Smoke  Alarm  should  be  promptly 
removed.

 

In  certain  circumstances  even  with  regular  cleaning,  contamination  can 
build  up  in  the smoke sensing chamber causing the  alarm  to sound. If this 
happens the  Smoke Alarm must be returned. Contamination is beyond  our 
control,  it  is  totally  unpredictable  and  is  considered  normal  wear  and  tear. 
For  this  reason,  contamination  is  not  covered  by  the  guarantee  and  a 
charge is made for all such servicing work.

 

 

WARNING: Do not paint your Alarm.

 

 

Finally, device must be replaced after 10 years of operation (check the 
“replace by” date marked on the side of the unit) 

 

Specifications

 

Dimensions

 

120mm x 120mm x 50mm

 

Weight

 

215g (with battery)

 

RF Range

 

1000m in open field

 

Battery

 

1 x 6LR61 9V Alkaline Battery 
or 1 x U9VL-J Lithium Battery

 

Operating voltage

 

9V

 

Battery life (typical)

 

1,5 years (Alkaline) / 3 years (Lithium)

 

Frequency

 

868MHz narrow band

 

Radio Protocols

 

ALPHA

 

Compatibility

 

Domonial 7/7G

 

Operating temperature

 

0° to +40° C

 

Approval Listing

 

EN14604

 

Battery fault signal (Supply 
voltage fault threshold)

 

Yes (7,2V)

 

Siren Output

 

85db(A) at 3m

 

Supervision

 

Yes

 

Sensing

 

Optical Smoke alarm

 

 

 
 
 

To obtain applicable CE compliance Declaration of Conformity, please refer to our web 
site : 

http://www.honeywell.com/security/emea/hscdownload

. For any additional 

information regarding the compliance of this product to any EU specific requirements 
or product warranty, please contact your local sales representative.

 

 
 

 

Honeywell Security

 

Honeywell Security & Communications 
1198, Avenue du Docteur Maurice Donat 

BP 1219

 

06254 MOUGINS CEDEX

 

 

Tel.: 

+33 (0)4 92 94 29 50 

Fax: 

+33 (0)4 92 94 29 60

 

www.honeywell.com

 

 

Honeywell is a registered  trademark  of Honeywell  International  Inc. All other 
trade- marks are the  properties  of their respective  owners.  All rights reserved.

 

 

 
 
 

 

 
800-05627 Rev: C

 

- 2 -

 

Reviews: