background image

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DFS8M 

- Installation Instructions

 

Wireless Optical Smoke Sensor with sounder

 

 

 

 

Introduction

 

 

The DFS8M is a wireless smoke 
sensor  designed  for Domonial  7 and

 

7G panels.  It features  a sounder 
for local signaling  of alarms and is 
used  as an early warning device.

 

 

 

Smoke alarm location

 

 

A single smoke sensor will give some 
protection if it is properly installed, but

 

 
 
 
 
 
 
 
 

 

DFS8M

 

5. Connect the battery to the battery snaps as shown in Figure 2

 

6. Register the device to the control panel by pressing the radio button (see 
registration paragraph)

 

7. Carefully line up the unit on the base, using the marks, and twist on as 
shown in Figure 3, then twisting it in a clock- wise direction (see Figure 1b). 
8. Press the Test button to ensure that the alarm works as shown in Figure 4.

 

 

Battery snaps

 

most homes will require two or more to ensure that a reliable early 
warning is given. For recommended protection, put one smoke sensor in 
all rooms (apart from kitchen and bathroom) where fire is most likely to 
break out.

 

If  only  one  smoke  sensor  is  installed,  it  should  be  located  between  the 
sleeping  area  and  the  most likely sources  of fire  (living room,  corridor for 
example), but it should not be more than 7,5 meters from the door to any 
room where a fire may start and block your escape from the house. Make 
sure that it can be heard loudly enough in the bedroom to wake someone. 
If your home has more than one floor, at least one Smoke Sensor should 
be fitted on each level. 
If the premise is one storey you should put your first Smoke Alarm in a 
corridor or hallway between the sleeping and living areas. Place it as near 
to the living area as possible, but make sure that it can be heard loudly 
enough in the bedroom to wake someone. 

 

Smoke alarm positioning 

 

 

Figure 1a

 

Smoke Sensor 

base

 

 
 

 

Test button                         

Figure 2

 

 

Figure 1b

 

Line up marks on base & cover

 

& rotate to click on    

Mounting plate

 

 
 
 
 

 

Radio button

 

Smoke rises towards the ceiling, then spreads out horizontally, 
therefore the ideal place to fix the sensor is in the middle of the room. 
When installing smoke alarms keep at least 30cm from walls and corners. 
Additionally, mount the unit at least 30cm from any light fitting or 
decorative object which might prevent smoke or heat entering the Smoke. 
With a sloping or peaked ceiling install a Smoke Alarm within 60cm of the 
peak (measured vertically). If this height is less than 60cm for Smoke 
Alarms the ceiling is regarded as being flat. 

 

Locations to avoid

 

 

 

 
 
 
 

Smoke head

 

 

 

 
 

• Bathrooms, kitchens, shower rooms, garages or other rooms where the 

smoke sensor may be triggered by steam, condensation, normal smoke 
or fumes. Keep at least 6 meters away from sources of normal 
smoke/fumes.

 

•  Locate  away  from  very  dusty  or  dirty  areas  as  dust  build-up  in  the 

chamber  can  impair  performance.  It  can  also  block  the  insect  screen 
mesh and prevent smoke from entering the smoke detector chamber.

 

• Do not locate in insect infested areas. Small insects getting into the 

smoke detector chamber can cause intermittent alarms.

 

 

• Places where the normal temperature can exceed 40°C or be below 0°C 

(e.g. attics, furnace rooms, directly above ovens or kettles etc.) as the 
heat/steam could cause nuisance alarms.

 

 

• Near a decorative object, door, light fitting, window moulding etc., that 

may prevent smoke or heat from entering the Alarm.

 

• Surfaces that are normally warmer or colder than the rest of the room 

(e.g. attic hatches). Temperature differences might stop smoke or heat 
from reaching the unit. 

• Next to or directly above heaters or air conditioning vents, windows, wall  
  vents etc. that can change the direction of airflow.

 

Tamperproofing the Alarms

 

The smoke head can be made tamperproof to prevent unauthorised removal.

 

Break  off  the  small  pillar  on  the  base  as  shown  in  figure  5.  To  remove  the 
smoke head from the ceiling it is now necessary to use a small screwdriver, to 
release  the  catch  (push  catch  towards  the  ceiling)  and  then  twist  off  the 
housing (see figure 6).

 

If  necessary  it  is  possible  to  further  secure  the  smoke  head  by  using  a  self 
tapping screw (2 to 3mm diameter and 6 to 8mm long - 

not supplied

), to firmly 

lock the smoke head and its mounting plate together (see figure 7).

 

Attach  the  smoke  head  to  the  mounting  plate.  Line  up  the  screw  (not 
supplied) on the “U” shaped recessed area shown in figure 7 and screw firmly 
home.

 

To remove the smoke head from the ceiling, remove the screw first, and use a 
small  screwdriver,  to  release  the  catch  (push  catch  towards  the  ceiling)  and 
then 

twist off in an anti-clock- wise direction. 

 

 

 

 

Push up catch & twist alarm anti- 

Break off small pillar 

clockwise  to remove

• In very high or awkward areas (e.g. over stairwells) where it may be 

difficult to reach the alarm (for testing, hushing or battery replacement).

 

• Locate the unit at least 1m from dimmer controlled lights and wiring as 

some dimmers can cause interference.

 

• Locate unit at least 1.5m from fluorescent light fittings as electrical 

“noise” and/or flickering may affect the unit.

 

Installation Procedure

 

1.  Select  a  location  complying  with  the  advice  given  in  the  paragraph 
“Smoke alarm location” and “Smoke alarm positioning”

 

2.  Remove  the  mounting  plate  from  the  sensor  by  twisting  it  in  an  anti-
clock- wise direction (see Figure 1a).

 

3.  Place  the  mounting  plate  on  the  ceiling  exactly  where  you  want  to 
mount the sensor. With a pencil, mark the location of the two screw holes.

 

4. Take care to avoid any electrical wiring in the ceiling, drill holes using a 
drill bit through the centre of the marked locations. Push the plastic screw 
anchors  into  the  drilled  holes.  Screw  the  mounting  plate  to  the  ceiling 
(screws  not  supplied).  Take  care  to  protect  the  detection  chamber  from 
dust during this operation.

 

 

 
 

 

           Figure 7

 

- 1 -

 

               Figure 3                                              Figure 4

 

               Figure 5                                          Figure 6

 