56
APT4000PH
Configuration
Controller
(for description see Pg 82 and the following)
Setpoint. Neutral zone
Relay 1 menu group
Relay 2 menu group
Controller setpoint
Enter neutral zone
(P) Controller gain
(I) Reset time T
R
(D) Rate time T
D
Pulse length/Pulse frequency
PLC: Pulse length
PFC: Pulse frequency
Hold behavior
L1.
L2.
Ct.
Relay / Controller
rL.
Code Display
Menu group
Select menu item
End:
Press
CONF
, then
ENTER
01.00 pH
(
XX.XX pH /
XXXX mV)
07.00 pH
(
XX.XX pH /
XXXX mV)
Setpoint
Select with
key, edit number with
key, proceed with
ENTER
Neutral zone (dead band)
Select with
key, edit number with
key, proceed with
ENTER
Controller: P-action component
Select with
key, edit number with
key, proceed with
ENTER
57
Code Display
Action
Choices
Ct.
0100 %
(0010 to
9999 %)
Controller: I-action component (reset
time). Select with
key, edit number
with key,
proceed
with
ENTER
0000 SEC
(0000 to
9999 SEC)
Controller: D-action component
(Rate time).
Select with
key, edit number with
key, proceed with
ENTER
0000 SEC
(0000 to
9999 SEC)
Pulse length/Pulse frequency
Select with
key,
proceed with
ENTER
PLC
(PFC)
PLC: Pulse length
Select with
key, edit number with
key, proceed with
ENTER
0010 sec
(0001 to
0600 SEC)
PFC: Pulse frequency
Select with
key, edit number with
key, proceed with
ENTER
0060
/min
(0001 to
0180 /min)
Behavior during Hold
Select with
key,
proceed with
ENTER
Y LAST
(Y Off)