5. Internal Memory Configuration and Functions
5.3. Operation parameters setting area
108
Resistance Temperature Detector 2MLF-RD4A User's Guide
R200
Honeywell
September 2010
Figure 62 – Setting error information
Address
Description
60
Channel 0 Setting Error Information Output
61
Channel 1 Setting Error Information Output
62
Channel 2 Setting Error Information Output
63
Channel 3 Setting Error Information Output
Input variation value/rate output (addresses 64–67)
1.
The amount of change in input temperature or variation rate (rate percentage based
on the sensor range) is saved. Every detection cycle of input variation alarm is
specified in the addresses 56–59.
2.
Monitoring with Special Module Monitoring is also available.
Figure 63 – Input variation value/rate output
Address
Description
64
Channel 0 Variation Value (Variation Rate) Output of Input Variation Alarm
65
Channel 1 Variation Value (Variation Rate) Output of Input Variation Alarm
66
Channel 2 Variation Value (Variation Rate) Output of Input Variation Alarm
67
Channel 3 Variation Value (Variation Rate) Output of Input Variation Alarm